AS-Interfaceinstallation
10
as-inTerface insTallaTiOn
10.1 as-interface connection
AS-Interface (Actuator Sensor Interface) is a field bus system which is used primarily for networking binary sensors
and actuators (slaves) with a higher-level control (master).
Bus line
Unshielded two-wire line (AS-Interface line as AS-Interface cable harness) along which both information (data) and
energy (supply voltage for the actuators and sensors) are transmitted.
network topology
Freely selectable within wide limits, i.e. star, tree and line networks are possible. Further details are described in the
AS-Interface specification (A/B slave model conforms to the version 3.0 specification).
10.2 Technical data for as-interface pcBs
Supply: via AS-Interface (24 V + 20 % / -10 %)
Outputs: 1 Valve Y1, max. 1 W, Power reduction after approx. 100 ms
with integrated Watch-Dog function
Certification: Certificate no. 87301 after version 3.0
10.3 programming data
I/O configuration
B hex
ID code
A hex (see below for bit configuration)
Extended ID code 1
7 hex
Extended ID code 2
E hex
Profile
S-B.A.E
Table 6:
Programming data
Bit configuration
Data bit
D3
D2
D1
D0
Input
0 Top not reached
1 Top reached
0 Bot not reached
1 Bot reached
–
–
Output
–
–
not used
0 Pilot valve OFF
1 Pilot valve ON
parameter bit
p3
p2
p1
p0
Output
not used
not used
not used
“0“ START Teach function
“1“ STOP Teach function
Table 7:
Bit configuration
english
Type 8695