beautypg.com

Approvals – Franklin Fueling Systems TS 550 evo Fuel Management System Programming Guide User Manual

Page 6

background image

6

Certified Programmer/Service Person: Only an FFS certified programmer or service person is allowed to access both 

the user interface keypad and areas internal to the Fuel Management System console.
Station Owner/Operator: The station owner or operator of the Fuel Management System console is only allowed to 

access the user interface keypad. Access to areas internal to the console is strictly prohibited.

Approvals

All Fuel Management System models are UL and cUL listed 6L79 as Liquid Level Gauge / Leak Detection

Systems. Third party approved leak detection — Pd (probability of detection) = 99.2 % for 0.1 or 0.2 gph leak tests

(0.1 = annual precision test, 0.2 is the monthly regulatory compliance test).

*The static tank test does not support Manifolded tanks.

**SCALD is 3rd party approved for up to three Manifolded tanks.

Substituting components could impair intrinsic safety. TS-550evo consoles are intrinsically safe

for sensors installed in – Class I, Division 1, Group D – hazardous locations. Substitution of

components could make the energy limiting circuitry in the system ineffective and could cause

an explosion hazard. Repairs to a TS-550 evo console or attached components should only be

performed by a qualified, factory-trained technician.

Warning