Displayed Alarm /

Warning

Device

Description

Recommended Actions

Over Speed

TPI

The STP controller is reporting an 

over speed condition.

Refer to the applicable Smart Controller Installation guide for details

Over Voltage

TPI

The STP controller is reporting an 

over voltage condition.

Pump Communication Fail

TPI

Communication from the TPI to 

the STP controller has failed.

Check all wiring connections and ensure that there is power supplied 

to the Smart Controller.

Pump In Water

TPI

The water level has risen to within 

3 inches of the programmed intake 

level.

Ensure proper programming of the TPI and calibration of the Smart 

Controller. If correct, have water removed from the tank

Relay Fault

TPI

The STP controller is reporting a 

relay fault error.

Refer to the applicable Smart Controller Installation guide for details.

Short Circuit

TPI

The STP controller is reporting a 

short circuit condition.

Unbalanced Load

TPI

The STP controller is reporting an 

unbalanced load condition.

Unbalanced Voltage

TPI

The STP controller is reporting an 

unbalanced voltage condition.

Under Voltage

TPI

The STP controller is reporting a 

voltage level under 200VAC.

Under Load

TPI

The STP controller is reporting an 

underload condition.

Unknown Fault

TPI

The STP controller is reporting an 

unknown fault code.

Check fault condition on Smart controller and contact FFS Technical 

Services for more information    

Printer Alarms

Check Printer

Printer

Printer is out of paper, or the 

printer door is open.

Make sure the printer has paper, and the printer door is closed 

completely.

Printer Head

Temperature

Printer

Print head high temperature 

persists for at least 2 minutes

Printer will resume printing and the alarm will clear after a short cool-

down period. Keep the console area cool and ventilated. If the alarm 

does not clear, contact FFS Technical Support. 

Printer Motor

Temperature

Printer

Printer motor has exceeded 

temperature limit

Allow printer to cool. Keep the console area cool and ventilated. If the 