Franklin Fueling Systems TS 550 evo Fuel Management System Programming Guide User Manual
Page 22
22
2-Wire Sensor Modules
The 2-Wire Sensor Module is designed to accept 12 sensor inputs per module, and the system as a whole can accept a
total of 36 sensors (3 modules with 12 inputs each). The module only supports standard sensors, and does not accept
inputs from any 3-wire sensor including BriteSensors
®
.
Group Name
Parameter Name
Parameter
Default
Description
Parameter
Input
2-Wire Sensor Modules
Module #
Channels
(0)
Number of channels in use per module.
0-12
Channel #
Name
(2-Wire Sensor
1)
Given name of channel.
abc #
Monthly Compliance
(Yes)
Select Yes if this sensor is to appear on the
Compliance page and in the Regulatory report
Yes / No
3-Wire Sensor Modules
The 3-Wire Sensor Module is designed to accept 8 sensor inputs per module, and the system as a whole can accept a
total of 24 sensors (3 modules with 8 inputs each). The 3WSNS can support standard sensors and BriteSensors
®
.
Group Name
Parameter
Name
Parameter
Default
Description
Parameter Input
3-Wire Sensor Modules
Module #
Channels
(0)
Number of channels in use
per module.
0 - 8
Channel #
Name
(3-Wire Sensor 1) Given name of channel.
abc #
Type
(Interstitial
(EIS) or 2-Wire
Sensor)
The type of sensor
connected to the channel.
After the Channels are
entered this will fill in
automatically.
Unknown,
Interstitial (EIS) or 2-Wire Sensor
Discriminating Interstitial Sensor (DIS)
Discriminating Dispenser Sump Sensor (DDS)
Discriminating Turbine Sump Sensor (DTS)
Monitoring Well Sensor (MWS)
Hydrostatic Interstitial Brine Reservoir Sensor (HIS)
Discriminating Monitoring Well Vapor Sensor (DVS)
Monthly
Compliance
(Yes)
Select Yes if this sensor
is to appear on the
Compliance page and in
the Regulatory report
Yes / No
4-20 mA and 4-20 mA EXP Input Modules
The Analog Input Module has 8 identical channels for loop powered IS sensors with a 4-20 mA interface.
The 4-20 mA EXP module is programmed in the same manner. The 420 EXP module is a non-intrisically safe board
located on the hazardous side of the console, must have the wires enclosed in explosion-proof conduit, and has a red
front. If a DTU is being used, there will be an option for a “virtual module” labeled Remote Module. The Remote Module
gathers information from the vapor pressure sensor whe n a DTU is used. (see DTU Programming for further details on
page 31 in this manual.)
Group Name
Parameter
Name
Parameter
Default
Description
Parameter Input
4-20mA Input Modules
Module #
Channels
(0)
Number of channels in use per module.
0-8
Channel #
Name
(4-20mA Input 1)
Given name of the channel.
abc #
Service Type
(Analog)
Determines the input signal.
Analog
Secondary Containment Monitoring
Line Leak Detection
Vapor Recovery Monitoring
FMS Level Probe
Low Range
-8.00
Low range of mA input
- #
High Range
8.00
High range of mA input
+ #