2-Wire Sensor Modules

The 2-Wire Sensor Module is designed to accept 12 sensor inputs per module, and the system as a whole can accept a 

total of 36 sensors (3 modules with 12 inputs each). The module only supports standard sensors, and does not accept 

inputs from any 3-wire sensor including BriteSensors

®

.

Group Name

Parameter Name

Parameter

Default

Description

Parameter

Input

2-Wire Sensor Modules

Module #

Channels

(0)

Number of channels in use per module.

0-12

Channel #

Name

(2-Wire Sensor 

1)

Given name of channel.

abc #

Monthly Compliance

(Yes)

Select Yes if this sensor is to appear on the 

Compliance page and in the Regulatory report

Yes / No

3-Wire Sensor Modules

The 3-Wire Sensor Module is designed to accept 8 sensor inputs per module, and the system as a whole can accept a 

total of 24 sensors (3 modules with 8 inputs each). The 3WSNS can support standard sensors and BriteSensors

®

.

Group Name

Parameter

Name

Parameter

Default

Description

Parameter Input

3-Wire Sensor Modules

Module #

Channels

(0)

Number of channels in use 

per module.

0 - 8

Channel #

Name

(3-Wire Sensor 1) Given name of channel.

abc #

Type

(Interstitial 

(EIS) or 2-Wire 

Sensor)

The type of sensor 

connected to the channel. 

After the Channels are 

entered this will fill in 

automatically. 

Unknown, 

Interstitial (EIS) or 2-Wire Sensor

Discriminating Interstitial Sensor (DIS)

Discriminating Dispenser Sump Sensor (DDS)

Discriminating Turbine Sump Sensor (DTS)

Monitoring Well Sensor (MWS)

Hydrostatic Interstitial Brine Reservoir Sensor (HIS)

Discriminating Monitoring Well Vapor Sensor (DVS) 

Monthly 

Compliance

(Yes)

Select Yes if this sensor 

is to appear on the 

Compliance page and in 

the Regulatory report

Yes / No

4-20 mA and 4-20 mA EXP Input Modules

The Analog Input Module has 8 identical channels for loop powered IS sensors with a 4-20 mA interface. 

The 4-20 mA EXP module is programmed in the same manner. The 420 EXP module is a non-intrisically safe board 

located on the hazardous side of the console, must have the wires enclosed in explosion-proof conduit, and has a red 

front. If a DTU is being used, there will be an option for a “virtual module” labeled Remote Module. The Remote Module 

gathers information from the vapor pressure sensor whe     n a DTU is used. (see DTU Programming for further details on 

page 31 in this manual.)

Group Name

Parameter

Name

Parameter

Default

Description

Parameter Input

4-20mA Input Modules

Module #

Channels

(0)

Number of channels in use per module.

0-8

Channel #

Name

(4-20mA Input 1)

Given name of the channel.

abc #

Service Type

(Analog)

Determines the input signal.

Analog

Secondary Containment Monitoring

Line Leak Detection

Vapor Recovery Monitoring

FMS Level Probe

Low Range

-8.00

Low range of mA input

- #

High Range

8.00

High range of mA input

+ #