beautypg.com

Approvals – Franklin Fueling Systems T5 Tank Sentinel Programming Guide User Manual

Page 6

background image

2

Certified Programmer/Service Person: Only an INCON certified programmer or service person is allowed to access

both the user interface keypad and areas internal to the Tank Sentinel

console.

Station Owner/Operator: The station owner or operator of the Tank Sentinel

console is only allowed to access the user

interface keypad. Access to areas internal to the console is strictly prohibited.

Approvals

All Fuel Management System models are UL and cUL listed 6L79 as Liquid Level Gauge / Leak Detection

Systems. Third party approved leak detection — Pd (probability of detection) = 99.2 % for 0.1 or 0.2 gph leak tests

(0.1 = annual precision test, 0.2 is the monthly regulatory compliance test).

*The static tank test does not support Manifolded tanks.

**SCALD is 3rd party approved for ONLY two Manifolded tanks.

Substituting components could impair intrinsic safety. TS-5XXXs are intrinsically safe for sensors

installed in – Class I, Division 1, Group D – hazardous locations. Substitution of components could

make the energy limiting circuitry in the system ineffective and could cause an explosion hazard.

Repairs to a TS-5XXX console or attached components should only be performed by a qualified,

factory-trained technician.

Warning