Displayed Alarm /

Warning

Device

Description

Recommended Actions

SN3 Sump Full

ChannelSN3 3-wire sensor detected

sump full of liquid.

Visually inspect location carefully for presence of liquid. In the case of

a leak, follow site policy procedures. If no liquid is present, and alarm

still exists, sensor may be tripped on error. Check wiring continuity from

sensor to console. Test sensor a

SN3 Sync Error

ChannelSN3 3-wire sensor data signals

not in sync with module.

Verify correct wiring.

SN3 Vapor

ChannelSN3 3-wire discriminate sensor

detecting vapors at location.

Visually inspect area for product presence.

SN3 Water

ChannelSN3 3-wire discriminate sensor

detecting water at location.

Visually inspect area for water presence.

Sudden Pressure Loss

Line

System detected sudden

pressure loss in line.

Follow site procedures for line leaks.

System Bus Error

None

Data transfer errors

occurred in the System

Bus. Suspect Bus at fault,

test and replace if found to

be inoperable.

Contact Franklin Fueling Systems’ Technical Services Dept. for support

on this issue. Follow safety procedures before working inside the cons

System memory error

Tank

Console memory at fault.

Contact Franklin Fueling Systems for support.

System Setup Error

None

Errors in the setup of the

system programming.

The console may need to be reprogrammed.

Tank Gross Leak Detected

Tank

Tank Gross leak test

detected tank. Suspect

possible leak.

Review tank leak test history and programming. Refer to Section

5: Misc./ Tank Leak Tests – Type and Frequency for instructions on

manually starting line leak tests.

Tank Leak Detected

Tank

Tank leak detected. Suspect

possible leak.

Review tank leak test history and programming. Refer to Section

5: Misc./ Tank Leak Tests – Type and Frequency for instructions on

manually starting line leak tests.

Tank SCALD Leak Detected

Tank

SCALD leak test detected

tank leak. Suspect possible

leak.

Review tank leak test history and programming. Review, why tank tests

fail (see …).

Tank Theft Detected

Tank

Product used in Sentinel

Mode exceeds theft limit

set. Suspect theft, and

then verify theft limit in

programming.

Verify theft limit in programming. Also obtain an accurate product level

and compare to inventory.

Temperature error

Tank

Special Probe RTD

temperature error detected.

Verify correct RTD table programming. If problem still exists, suspect

wiring or faulty probe.

Ullage error

Tank

Ullage reported has

exceeded tank capacity.

Verify correct Tank Chart programming.

Unstable probe

Tank

LL Liquid Level probes can

send inconsistent data back

to console.

Test probe communications by connecting the probe directly to the

console.

Water volume error

Tank

Water volume has

exceeded tank capacity.

Verify actual water volume. Verify programming as well.