Franklin Fueling Systems T5 Tank Sentinel Programming Guide User Manual
Page 27
23
AC Input Modules
Group Name
Parameter Name
Parameter
Value
Description
Max Value
AC Input Modules
Number Gasoline Hooks per Dispenser
(2)
Including diesel.
1-8
Module #
Channels
(0)
Number of channels in use per module.
1-12
Channel #
Name
(AC Input 1)
Given name of channel.
abc#
Enabled
(Yes)
Yes if channel is used.
Yes/No
Active High
(Yes)
Yes will activate channel when high voltage
is present. No will activate channel with no
voltage present.
Yes/No
Probe Modules
Group Name
Parameter Name
Parameter Value
Description
Max Value
Probe Modules
Module #
Channels
(0)
Number of channels in use per module.
1-12
Channel #
Name
(Probe 1)
Given Name of Probe.
abc#
Enabled
(Yes)
Yes if this probe channel is used.
Yes/No
Type
(TS-LL2)
Type of probe connected.
TS-VFM
TS-LL2
Unknown
2-Wire Sensor Modules
Group Name
Parameter Name
Parameter Value
Description
Max Value
2-Wire Sensor Modules
Module #
Channels
(0)
Number of channels in use per module.
1-12
Channel #
Name
(2-Wire Sensor 1)
Given name of channel.
abc#
Enabled
(Yes)
Yes if this channel is used.
Yes/No
3-Wire Sensor Modules
Group Name
Parameter Name
Parameter Value
Description
Max Value
3-Wire Sensor Modules
Module #
Channels
(0)
Number of channels in use per module.
1-12
Channel #
Name
(2-Wire Sensor 1)
Given name of channel.
abc#
Enabled
(Yes)
Yes if the channel is used.
Yes/No
4-20 mA Input Modules
Group Name
Parameter
Name
Parameter Value
Description
Max Value
4-20mA Input Modules
Module #
Channels
(0)
Number of channels in use per module.
1-8
Channel #
Name
(4-20mA Input 1)
Given name of the channel.
abc#
Enabled
(Yes)
Yes if the channel is in use.
Yes/No
Service Type
(Analog)
Determines the output signal.
Analog
SCM
LLD
Low Range
(-5)
Low voltage level of output signal.
#
High Range
(5)
High voltage level of output signal.
#
Log Data
(No)
Used to log signal data.
Yes/No