Franklin Fueling Systems T5 Tank Sentinel Programming Guide User Manual
Page 30

26
Manifold Tank System
Group Name
Parameter Name
Parameter Value
Description
Max Value
Fuel Management System
Tanks
Number of Tanks
(0)
Number of tanks in fuel system.
0-48
Tank #
Name
(Tank 1)
Given name of the tank.
abc#
Type
Special 1
Type of tank used.
Std/Spcl
Manifolded
(No)
Enable a manifold.
Yes/No
Manifold #
(1)
Number of manifold.
1-24
Manifolds
Manifold #
Name
(Manifold 1)
Given name of manifold.
abc#
Product #
(1)
Number of product in tanks.
1-48
Delivery Threshold
(200.0 gal)
Amount of increase to detect delivery.
# gal
Theft Threshold
(5.0 gal)
Amount of decrease to detect theft.
# gal
Group Name
Parameter Name
Parameter Value
Description
“From” Address
Address of sender (console).
SMTP Host
your_smtp_host_address
IP address of SMTP Host.
SMTP Port
25
Port address of SMTP.
Enable Authentication
No
Data authentication (if required).
Maximum Queue Size
20
Maximum size of queue in Megabytes.
Retry Timeout
3600
Time, in seconds, that the console will wait before attempting to resend the
message.
Watchdog Timeout
30
Time, in seconds, that the console self-monitoring program waits when it
expects and error due to software or power quality problems.
Events
Group Name
Parameter Name
Parameter Value
Description
Options
Rules
Rule – New Rule #
Name
(New Rule #)
Given name of rule.
abc#
Enabled
(No)
Yes to enable rule.
Yes/No
Events
Event
Type
(New Alarm Occurred)
Event type that triggers action.
New Alarm Occurred;
Alarm Status Changed;
Application Event;
Scheduled
Category
(Any)
System that event occurs in to trigger
action.
Any;
System;
FMS;
VRM;
SCM;
Other
Code
(Any)
Error/Trouble Event Code that triggers
action.
(see below)
Device
(Any)
Device that created the alarm
condition.
Various
State
(Any)
State of alarm to trigger action.
Various