Programming Modules
The Fuel Management System is composed of a custom set of modules. Each module maintains individual
characteristics. Parameters must be set to match the site configuration. The programming table below will assist in this
setup.
Power Supply
Group Name
Parameter Name
Parameter
Value
Description
Max Value
Power Supply
RS-485
Enable Interface
(No)
Enables TS-DIM options.
Yes/No
TS-DIM
Enable Interface
(No)
Enables DIM Communications options.
Yes/No
Communication
Baud Rate
(9600)
Data transmission speed in bits per second.
1200-57600 bps
Data Bits
(8)
Number of bits that represent data.
7-8
Parity
(None)
Value of parity (error check) bit.
None, Even,
Odd
Stop Bits
(1)
Number of stop bits, notifies receiving device of
end of data packet.
1-2
Response Timeout
(8)
Period of time the device will wait until
transmission stops in seconds.
1-10
Precision
(2)
?
1-8
Fuel Points
Number of Fuel Points
(0)
Number of fueling points on site.
1-32
Fuel Point #
Number of Meters
(0)
Number of meters at site.
1-8
Meter #
Grade
(1)
Type of product flowing through meter.
1-8
RS-232
Baud Rate
(9600)
Data transmission speed in bits per second.
1200-57600
Data Bits
(8)
Number of bits that represent data.
7-8
Parity
(None)
Value of parity (error check) bit.
None, Even,
Odd
Stop Bits
(1)
Number of stop bits, notifies receiving device of
end of data packet.
1-2
Response Timeout
(8)
Period of time the device will wait until
transmission stops in seconds.
1-10
Relays
Channel #
Name
(Relay 1)
Given name of the relay.
abc#
Enabled
(Yes)
Whether the Relay is Enabled or not.
Yes/No
Type
(Unknown)
Equipment connected to the relays output.
Unknown
Submersible
Alarm
Solenoid
Dispenser
Other
Polarity
(Normal)
Allows the polarity to be inverted.
Normal, Invert
Logic
(OR Logic)
The type of logic that the gate will use to process
incoming signals. In OR, if any combination of
inputs is active, the relay is active. With AND,
when all inputs are active, the relay is active. In
XOR, if all inputs are in the same state (on/off), the
relay is inactive.
OR, AND, XOR
Physically Wired As
(Normally Open)
How the relay is wired internally.
NO, NC
Number of inputs
(0)
This adjusts the circuit to accommodate incoming
signal levels.
1-32
Input #
Type
(Unknown Module) Chooses which module is inputting the signal to
the relay.
Unknown
Controller
Power Supply
Probe
2-wire Sensor
3-wire Sensor
Low Voltage Inputs
Channel #
Name
(LV Input 1)
Given name of input.
abc#
Enabled
(Yes)
Whether the input is Enabled or not.
Yes/No