GE Industrial Solutions AF-300E$ User Manual
Page 74

LCD
GRAPHIC
FACTORY
FUNCTION
DISPLAY
SETTING
DESCRIPTION
SETTING
6-17
FMA
11
Adjustment
Range
ANALOG MONITOR OUTPUT
* 43
FMP PULSES
FMP FREQUENCY PULSE OUTPUT
24
The FMP terminal provides a pulse whose
output is proportional to drive output
frequency. The number of pulses per
second is given as output Hz multiplied by
the setting in Function Code 43 with a
maximum output of 6,000 pulses per second.
Function Code 43 is adjustable from 6 to
100. The output frequency is accurate to
within
±
1 %. Ex: 60Hz, setting 24 – 60x24 = 1440 pulses.
* 44
FMP V-ADJ
FMP VOLTAGE ADJUST
100
The average voltage of the FMP terminal
pulsed output can be adjusted from approxi-
mately 5 to 12 VDC by changing Function Code
44 from 50 to 120, respectively. The voltage
will be accurate to
±
5%. The peak voltage
of the pulses will be approximately 15.6 VDC
regardless of this setting, only the average
output voltage is changed. Ex: V
avg.
= 12V x 100 setting = 10V
120
CAUTION: The minimum load impedance which should be
placed between the FMP and CM terminals is 5,000 ohms.
* 45
FMA V-ADJ
FMA VOLTAGE ADJUST
100
The FMA terminal provides a 0 to +10 VDC
analog output which can indicate output
frequency, current, torque, or power (see
Function Code 46). This Function Code can
be used to adjust the voltage output by a
factor of 0.65 to 2.00 (note that the max-
imum available output is 10.3 VDC).
Adjustable from 65 to 200% for 10.3VDC output.