230v, 460v – GE Industrial Solutions AF-300E$ User Manual
Page 34

4-3
Table 4: AF-300E$ Drive Cable Size Recommendations & Circuit Protection Rating
230V
DB UNIT &
INCOMING POWER
HP
CURRENT
POWER
DC LINK REACTOR
AC-LINE DEVICE
2
CONST
VAR
CONST
VAR
CABLE AMP
CABLE
AMP
CIRCUIT
TRQ
TRQ
TRQ
TRQ
AWG
QTY
TERMINAL #
AWG
1
QTY
TERMINAL #
FUSES
BREAKER
0.5
0.5
3
3
16
1
–
14
1
–
6
15
1
1
5
5
16
1
–
14
1
–
10
15
2
2
8
8
14
1
–
14
1
–
15
15
3
3
11
11
14
1
–
14
1
–
20
20
5
5
17
17
10
1
–
10
1
–
30
30
7.5
10*
25
29
8
1
–
8
1
–
60
50
10
15*
33
42
6
1
–
6
1
–
80
60
15
20*
46
55
4
1
–
4
1
–
100
75
20
25*
59
68
2
1
–
2
1
–
125
100
25
30*
74
80
1
1
–
2
1
–
150
125
30
87
1
1
–
1/0
1
–
150
150
460V
DB UNIT &
INCOMING POWER
HP
CURRENT
POWER
DC LINK REACTOR
AC-LINE DEVICE
2
CONST
VAR
CONST
VAR
CABLE
AMP
CABLE
AMP
CIRCUIT
TRQ
TRQ
TRQ
TRQ
AWG
QTY
TERMINAL #
AWG
1
QTY
TERMINAL #
FUSES
BREAKER
1
1
2.5
2.5
16
1
–
14
1
–
6
5
2
2
3.7
3.7
16
1
–
14
1
–
10
10
3
3
5.5
5.5
16
1
–
14
1
–
15
15
5
5
9
9
14
1
–
14
1
–
15
15
7.5
10 *
13
16.5
10
1
–
14
1
–
30
30
10
15 *
18
23
10
1
–
14
1
–
40
30
15
20 *
24
30
8
1
–
14
1
–
50
40
20
25 *
30
37
6
1
–
14
1
–
60
50
25
30 *
39
44
6
1
–
14
1
–
80
60
30
45
45
4
1
–
12
1
–
80
75
40 *
45
52
4
1
31812
12
1
321600
80
100
40
50 *
60
66
2
1
321600
12
1
321868
100
100
50
60 *
75
77
1/0
1
321868
10
1
31812
125
125
60
75 *
91
96
1/0
1
321868
8
1
321600
150
150
75
100 *
112
124
1/0
1
321868
6
1
321600
175
150
100
125 *
150
156
3/0
1
36927
6
1
321878
175
200
125
150 *
176
180
1/0
2
321868
6
1
321868
200
200
150
200 *
210
253
1/0
2
321868
4
1
36923
300
225
200
250 *
304
304
3/0
2
36929
4
2
171500-2
350
400
250
300 *
377
377
250
2
171500-2
4
2
171502-2
400
400
300
350 *
415
415
300
2
171500-2
4
2
171502-2
500
500
* In variable torque applications, Function Code 86 (Motor Hp Capacity) needs to be changed to Set Drive Hp vs. Load Hp.
40 Hp and above is 460-480 VAC input, VT applications only.
1 Device ratings such as system coordination, short-circuit rating and type must be carefully reviewed by the user.
2 Based on GE Fuji DB resistor designs. Other ratings require careful review.
3 Device ratings such as system coordination, short-circuit rating and type must be carefully reviewed by the user.
Note: Wire size from NEC table 310-16. Copper wire rated 60 Deg. C for 100 amps or less, 75 Deg. C for over 100 amps in 30 Deg. C
ambient and 1.25 times Drive rated amps. These are minimum wire sizes; consult and conform to local and national codes.
CAUTION: The grounding connector shall be sized in accordance with the NEC or Canadian Electrical Code. The connection shall be made
by a UL listed or CSA certified closed-loop terminal connector sized for the wire gauge involved. The connector is to be fixed using the
crimp tool specified by the connector manufacturer.
Recommend GE Spectra RMS MAG-BREAK Circuit Breakers.
CAUTION: Quick-acting bussman JKS or equivalent J-class AC line fuses are required on 30 Hp or lower Drives. Check local electrical codes
for 40 Hp and higher.