Page
147
7.2 Point-to-Point Serial to Xtreme I/O
7.2.1 Use Case Parameters
In this parameter, a radio modem is being used to connect PLC or similar device to a
remote Xtreme I/O module.
1. Wire the radio modem input and power as described in section three.
2. Configure the radio modem as described in section 7.1.1.1.
3. Configure the I/O module radio settings to match the radio modem.
4. Channel Number must match the channel selected in section 7.3 step 6.
5. Network identifier must match the network identifier selected in section 7.1.1.1 step 7.
6. Set the Modem RF data rate to match the I/O module. On the Advanced Modem
Settings tab, under the RF interfacing tab, click on BR- RF Data Rate and set the
desired data rate from the pull down menu.
7. If encryption is being used, the same key must be used in the I/O module. The radio
modem uses a hexadecimal string. When entering your key in the I/O module, you
must enter it in HEX.
8. It is recommended that you bench test your configuration before installing it in the
field.