beautypg.com

Bip4: smoke input 98, Bip1: external interlock 98, Bip3: occupied/unoccupied – Trane LO User Manual

Page 98: Mode 98, Terminal unit control (tuc)

background image

Terminal Unit
Control (TUC)

98

UNT-IOM-6

BIP4: Smoke Input

BIP3: Occupied/
Unoccupied Mode

BIP1: External
Interlock

and the electric heat to disable. This creates an immediate shutdown

latching diagnostic, which requires a manual or Tracer

â

reset to

resume normal operation.

However, normal operation cannot resume until the water level

recedes to an acceptable level. The switch will close after the water

level recedes, and the active temperature control of the unit will

resume by an automatic reset. Since both the condensate overflow

detection and occupied/unoccupied status occupy BIP3 on the TUC

board, only one option can be in use. The factory configures the 24V

dry contact input as normally closed to indicate an alarm. However, it

also can be normally open if using the correct switch.

The smoke input is a binary input on the TUC that is used with a

smoke detector switch (installer supplied) to signal an alarm. Config-

ure the input to either send an alarm to Tracer

®

or as a shutdown

latching diagnostic. If the input is configured as a shutdown latching

diagnostic, the TUC closes the control valve(s), shuts the fan off,

closes the fresh air damper, and disables electric heat.

If the input is configured to send an alarm, Tracer will issue a system

wide shutdown for the building. The unit will continue to run, and no

diagnostic will register within the TUC. The factory configures the

24V dry contact input as normally closed. However, it can also be

normally open if using the correct switch.

The unit can operate in the occupied/unoccupied mode when a

binary signal is input from an external source such as a time clock or

Tracer

®

. Reference the “TUC Fan Mode Operation” section on page

65 for the sequence of operations. This option is only available if the

condensate overflow input is not in use (if not using Tracer

®

), since

both inputs occupy the same point on the TUC board. The factory

configures the 24V dry contact input as normally closed. However, it

can also be normally open if using the correct switch. A closed

signal indicates occupied mode.

The external interlock input allows the unit to be remotely stopped

when a binary signal is input to the TUC from an external source or

from Tracer

®

. Since both external interlock and condensate overflow

input to the same point (if not using Tracer

®

) on the TUC board, only

one input can be in use. The factory configures the 24V dry contact

input as normally closed, but it can also be open if using the correct

switch.