Page 35: Tions 35, Electrical grounding restrictions, Wall mounted control interconnection wiring

background image

UNT-IOM-6

35

Table 3. Maximum Wiring Distances, ft (m)
Device

Wire Size Range

Max. Wiring Distance

Fan Mode Switch 14 - 22 AWG
500 (152.4)
Zone Sensor Module 16 - 22 AWG

200 (60.96)

All sensor and input circuits are normally at or near ground (common)

potential. When wiring sensors and other input devices to the Tracer

®

ZN.010, ZN.510, ZN.520 or TUC, avoid creating ground loops with

grounded conductors external to the unit control circuit. Ground loops

can affect the measurement accuracy of the controller.

CAUTION: Unit transformer IT1 provides power to

fan-coil unit only. Field connections to the transformer
IT1 may create immediate or premature unit component
failure.

All input/output circuits (except isolated relay contacts and optically

isolated inputs) assume a grounded source, either a ground wire at

the supply transformer to control panel chassis, or an installer

supplied ground.

Note: Do not connect any sensor or input circuit to an external ground

connection.

The installer must provide interconnection wiring to connect wall

mounted devices such as a fan mode switch or zone sensor module.

Refer to the unit wiring schematic for specific wiring details and point-

to-point wiring connections. Dashed lines indicate field wiring on the

unit wiring schematics. All interconnection wiring must conform to

NEC Class 2 wiring requirements and any state and local require-

ments. Refer to Table 3 for the wire size range and maximum wiring

distance for each device.

Recommendation: Do not bundle or run interconnection wiring

in parallel with or in the same conduit with any high-voltage

wires (110V or greater). Exposure of interconnection wiring to

high voltage wiring, inductive loads, or RF transmitters may

cause radio frequency interference (RFI). In addition, improper

separation may cause electrical noise problems. Therefore, use

shielded wire (Beldon 83559/83562 or equivalent) in applications

that require a high degree of noise immunity. Connect the shield

to the chassis ground and tape at the other end.