Tracer® communication wiring, Terminal unit control (tuc), Tracer – Trane LO User Manual

Page 88: Communication wiring

background image

Terminal Unit
Control (TUC)

88

UNT-IOM-6

For TUC controlled units that will interface with the Trane Tracer

®

system or Tracer Summit

®

building management system, terminate

the communication wiring in the control box at the designated

terminals on the low voltage terminal strip. Reference the unit wiring

schematic or submittals.

Take care to maintain the correct polarity throughout the communica-

tion wiring circuit.

Ground shields at each TUC, taping the opposite end of each shield

to prevent any connection between the shield and another ground.

Refer to Trane publication, EMTX-IOP-1 Installation Operation and

Programming Guide, for the communication wiring diagram.

Communication wire must conform to the following specification:

· Shielded twisted pair 18 AWG

· Capacitance 23 (21-25) picofarads (pF) per foot

· Listing/Rating - 300V 150C NEC 725-2 (b) Class 2 Type

CL2P

· Trane Part No. 400-20-28 or equivalent, available through

Trane BAS Buying Group Accessories catalog

Follow these general guidelines when installing communication

wiring:

· Maintain a maximum 5000 ft. aggregate run

· Install all communication wiring in accordance with the

NEC and all local codes.

· Solder the conductors and insulate (tape) the joint suffi-

ciently when splicing communication wire. Do not use wire

nuts to make the splice.

· Do not pass communication wiring between buildings

because the unit will assume different ground potentials.

· Do not run power in the same conduit or wire bundle with

communication link wiring.

Tracer

®

Communication
Wiring