ZN.010 and ZN.510

The Tracer

®

ZN.010

is a stand-alone

device that controls

fan-coils and cabinet

heaters. The Tracer

®

ZN.510 can be

stand-alone or utilize

peer-to-peer commu-

nications. The

controller is easily

accessible in the

control end panel for

service. The control

end panel is on the

end of the unit

opposite the piping.

Reference Figure 27.

Figure 27. The Tracer ZN.010 board.

Sequence of Operations
Off
: Fan is off; control valves and fresh air damper option close. Low

air temperature detection option is still active.

Auto (Fan Cycling): Fan and fresh air damper cycle with control

valve option to maintain setpoint temperature. In cooling mode, the

fan cycles from off to medium and in heating mode it cycles from off

to low. When no heating or cooling is required, the fan is off and the

fresh air damper option closes.

Low/Med/High (Continuous Fan): Fan operates continuously while

control valve option cycles to maintain setpoint temperature. Fresh