UNT-IOM-6

warm enough to heat when it is five degrees above the measured

space temperature.

When the controller invokes the entering water temperature sampling

function, the unit opens the main hydronic valve for no more than

three minutes before considering the measured entering water

temperature. An initial stabilization period is allowed to flush the coil.

This period is equal to 30 seconds plus ½ the valve stroke time. Once

this temperature stabilization period has expired, the controller

compares the entering water temperature against the effective space

temperature (either hardwired or communicated) to determine whether

the entering water can be used for the desired heating or cooling. If

the water temperature is not usable for the desired mode, the control-

ler continues to compare the entering water temperature against the

effective space temperature for a maximum of three minutes.

The controller automatically disables the entering water temperature

sampling and closes the main hydronic valve when the measured

entering water exceeds the high entering water temperature limit (110

F). When the entering water temperature is warmer than 110 F, the

controller assumes the entering water temperature is hot because it

is unlikely the coil would drift to a high temperature unless the actual

loop temperature was very high.

If the entering water temperature is unusable — too cool to heat or

too warm to cool — the controller closes the hydronic valve and waits

60 minutes before initializing another sampling. If the controller

determines the entering water temperature is valid for heating or

cooling, it resumes normal heating/cooling control and effectively

disables entering water temperature sampling until it is required.

The Tracer

®

ZN.520 controller supports 1- or 2-stage electric heat

operation for heating. To control the space temperature, electric heat

is cycled to control the discharge air temperature. The rate of cycling

is dependent upon the load in the space and the temperature of the

incoming fresh air from the economizer (if any).Two-pipe changeover

units with electric heat use the electric heat only when hot water is

not available.

Manual

Units with the manual fresh air damper option ship with the damper in

the closed position, which is adjustable from zero to 100 percent in

25 percent increments. To adjust the position, first remove the air filter

Electric Heat Operation

Fresh Air Damper

Options