beautypg.com

Tracer, Zn.520 – Trane LO User Manual

Page 62

background image

Tracer

®

ZN.520

62

UNT-IOM-6

When the controller is in the occupied mode, the unit attempts to

maintain the space temperature at the active occupied heating or

cooling setpoint, based on the measured space temperature, the

discharge air temperature, the active setpoint, and the proportional/

integral control algorithm. The modulating control algorithm used

when occupied or in occupied standby is described in the following

sections. Additional information related to the handling of the control-

ler setpoints can be found in the previous Setpoint operation section.

When the controller is in the unoccupied mode, the controller at-

tempts to maintain the space temperature at the stored unoccupied

heating or cooling setpoint, based on the measured space tempera-

ture, the active setpoint and the control algorithm, regardless of the

presence of a hardwired or communicated setpoint. Similar to other

configuration properties of the controller, the locally stored unoccu-

pied setpoints can be modified using Rover™ service tool.

In unoccupied mode, a simplified zone control algorithm is run. During

the cooling mode, when the space temperature is above the cool

setpoint, the primary cooling capacity operates at 100%. If more

capacity is needed, the supplementary cooling capacity turns on (or

opens to 100%). During the heating mode, when the space tempera-

ture is below the heat setpoint, the primary heating capacity turns on.

All capacity is turned off when the space temperature is between the

unoccupied cooling and heating setpoints. Note that primary heating

or cooling capacity is defined by unit type and whether heating or

cooling is enabled or disabled. For example, if the economizer is

enabled and possible, it will be the primary cooling capacity. If

hydronic heating is possible, it will be the primary heating capacity.

The controller can be placed into the occupied standby mode when a

communicated occupancy request is combined with the local

(hardwired) occupancy binary input signal. When the communicated

occupancy request is unoccupied, the occupancy binary input (if

present) does not affect the controller’s occupancy. When the

communicated occupancy request is occupied, the controller uses

the local occupancy binary input to switch between the occupied and

occupied standby modes.

During occupied standby mode, the controller’s economizer damper

position goes to the economizer standby minimum position. The

economizer standby minimum position can be changed using Rover

service tool.

In the occupied standby mode, the controller uses the occupied

Occupied

Unoccupied Mode

Occupied Standby Mode