Page 29

background image

UNT-IOM-6

29

The manual circuit setter valve is an optional end valve supplied on

the return pipe of the factory piping package. The valve allows the

operator to regulate water flow through the hydronic coil, balance the

water flow through the unit with other units in the piping system, and

serves as a shutoff or end valve. See Figure 17.

Follow the procedure below to set maximum water flow through the

coil.

1. Establish water flow through the coil. Perform an open override of

the valve if the control valve is closed to the coil, either manually or

by Tracer

®

.

If the piping package has 2-position, normally closed valves:

Drive open the valve using a 24V signal.

If the piping package has 2-

position, normally open

valves:

Manually drive open the valve by

removing power to the valve.

If the piping package has

modulating valves:

To manually drive the valve open,

depress the button stem on top

of the valve and push the lever

located on the side of the valve to

the full open position.

2. For presetting, use the appropriate valve curve shown in Figure 19

on page 30 to determine which setting is necessary to achieve the

appropriate pressure drop.

3. Carefully remove the Schrader pressure port connection caps on

the manual circuit setter, since they will be at the same temperature

as the pipeline.

4. Bleed all air from the hoses and meter before reading the pressure

drop. Refer to the gauge operating instructions.

5. Adjust the circuit setter valve by turning the valve stem until the

appropriate pressure drop is achieved. See Figure 18 on page 30.

6. After achieving the proper setting, slightly loosen the two socket

head cap screws and rotate the memory stop around until it

touches the back side of the indicator. Then tighten the screws to

Figure 17. Manual circuit setter
valve.

Balancing The Manual
Circuit Setter Valve