Tracer, Zn.520 – Trane LO User Manual

Page 74

background image

Tracer

®

ZN.520

74

UNT-IOM-6

Binary outputs are configured to support the following:

• Three fan stages (when one or two fan stages are present, medium

fan speed can be configured as exhaust fan)

• One hydronic cooling stage

• One hydronic heating stage (dehumidification requires this to be in

the reheat position)

• One DX cooling stage

• One- or two-stage electric heat (dehumidification requires this to be

in the reheat position)

• Face and bypass damper

• Modulating outdoor air damper

• One baseboard heat stage

Table 27. Binary Output Configuration
Binary Output

Configuration

J1-1

Fan high

J1-2

Fan medium

J1-3

Fan low

J1-4

(Key)

J1-5

Cool valve – open, or 2 position valve,

(Note 1)

J1-6

Cool valve – close (Note 1)

J1-9

Heat valve – open, or 2 position valve, or 1

st

Electric heat stage (Note 1)

J1-10

Heat valve – close or 2

nd

Electric heat stage

(Note 1)

J1-11

Fresh air damper - open

J1-12

Fresh air damper - close

TB4-1

Generic / Bbaseboard heat output

TB4-2

24VAC

Note 1: For Tracer

®

ZN.520 units configured and applied as 2-pipe

hydronic heat/cool changeover, terminals J1-5 and J1-6 are used to

control the primary valve for both heating and cooling. For Tracer

®

ZN.520 units configured and applied as 2-pipe hydronic heat/cool

changeover with electric heat, terminals J1-5 and J1-6 are used to

control the primary valve (for both cooling and heating), and terminals

J1-9 and J1-10 are used only for the electric heat stage. For those 2-

pipe changeover units, electric heat will not be energized while the

hydronic supply is hot (5 or more degrees above the space tempera-

ture).

Binary Outputs