beautypg.com

Tracer, Zn.520, Zone sensor – Trane LO User Manual

Page 76

background image

Tracer

®

ZN.520

76

UNT-IOM-6

The Tracer

®

ZN.520 controller accepts the following zone sensor

module inputs:

• Space temperature measurement (10kW thermistor)

• Local setpoint (either internal or external on the zone sensor

module)

• Fan switch

• Timed override (On) and Cancel timed override

• Communication jack

Trane zone sensors use a 10kW thermistor to measure the space

temperature. Typically, zone sensors are wall-mounted in the room

and include a space temperature thermistor. As an option, the zone

sensor can be unit-mounted with a separate space temperature

thermistor located in the unit’s return air stream. If both a hardwired

and communicated space temperature value exist, the controller

ignores the hardwired space temperature input and uses the commu-

nicated value.

Zone sensors with an external setpoint adjustment (1kW) provide the

Tracer

®

ZN.520 controller with a local setpoint (50 to 85 F or 10 to

29.4 C). The external setpoint is exposed on the zone sensor’s front

cover.

When the hardwired setpoint adjustment is used to determine the

setpoints, all unit setpoints are calculated based on the hardwired

setpoint value, the configured setpoints, and the active mode of the

controller. The hardwired setpoint is used with the controller’s occu-

pancy mode (occupied, occupied standby, or unoccupied), the

heating or cooling mode, the temperature deadband values, and the

heating and cooling setpoints (high and low limits) to determine the

controller’s active setpoint.

When a building automation system or other controller communicates

a setpoint to the controller, the controller ignores the hardwired

setpoint input and uses the communicated value. The exception is

the unoccupied mode, when the controller always uses the stored

default unoccupied setpoints. After the controller completes all

setpoint calculations, based on the requested setpoint, the occu-

pancy mode, the heating and cooling mode, and other factors, the

calculated setpoint is validated against the following setpoint limits:

• Heating setpoint high limit

• Heating setpoint low limit

• Cooling setpoint high limit

• Cooling setpoint low limit

Zone Sensor

Space Temperature

Measurement

External Setpoint Adjustment