On a transition from off to any other fan speed, the Tracer

®

ZN.520

controller automatically starts the fan on high speed and runs the fan

at high speed for 0.5 seconds. This provides the ample torque

required to start all fan motors from the off position.

Tracer

®

ZN.520 can sample the entering water temperature for all

hydronic main coil changeover units.Hydronic heating/cooling

changeover operation requires central plant operation, and the unit

controller must use an entering water temperature sensor to verify

delivery of the desired water temperature from the central plant.

When three-way valves are ordered with a Tracer

®

ZN.520 control, the

controller is factory-configured to disable the entering water tempera-

ture sampling function, and the entering water sensor is mounted in

the proper location. Disabling entering water temperature sampling

eliminates unnecessary water flow through the main coil when three-

way valves are used.

The Tracer

®

ZN.520 controller offers a control solution for two-way

valve applications that does not require special unit considerations,

such as those required by bleed lines. The controller includes an

entering water temperature sampling function that periodically opens

the two-way valve to allow temporary water flow, producing reliable

entering water temperature measurement.

.

Only units using the main hydronic coil for both heating and cooling

(2-pipe changeover and 4-pipe changeover units) use the entering

water temperature sampling function. Two-pipe changeover and 4-pipe

changeover applications allow the main coil to be used for heating

and for cooling; therefore, these applications require an entering water

temperature sensor.

The entering water temperature value is useful to the unit controller

only when heating or cooling is required. The entering water tempera-

ture must be five degrees above the space temperature for hydronic

heating and five degrees below the space temperature for hydronic

cooling. When water flows normally and frequently through the coil,

the controller does not invoke the sampling function because the

water temperature is satisfactory for the desired heating or cooling.

The controller invokes entering water temperature sampling only when

the measured entering water temperature is too cool to heat or too

warm to cool. Entering water is cold enough to cool when it is five

degrees below the measured space temperature. Entering water is

Fan Start on High Speed

Entering Water

Temperature

Sampling Function

Heating or Cooling Required