Tracer, Zn.520, Data sharing – Trane LO User Manual

Page 72

background image

Tracer

®

ZN.520

72

UNT-IOM-6

Dehumidification is possible when mechanical cooling is available,

the heating capacity is located in the reheat position, and the space

relative humidity setpoint is valid.The controller starts dehumidifying

the space when the space humidity exceeds the humidity setpoint.

The controller continues to dehumidify until the sensed humidity falls

below the setpoint minus the relative humidity offset.The controller

uses the cooling and reheat capacities simultaneously to dehumidify

the space. While dehumidifying, the discharge air temperature is

controlled to maintain the space temperature at the current setpoint.

A typical scenario involves high humidity and high temperature load of

the space.The controller sets the cooling capacity to 100% and uses

the reheat capacity to warm the discharge air to maintain space

temperature control.Dehumidification may be disabled via Tracer or

configuration.

Note: If the unit is in the unoccupied mode, the dehumidification

routine will not operate.

Because this controller utilizes LonWorks™ technology, the control-

ler can send or receive data (setpoint, heat/cool mode, fan request,

space temperature, etc.) to and from other controllers on the commu-

nication link, with or without the existence of a building automation

system. This applies to applications where multiple unit controllers

share a single space temperature sensor (for rooms with multiple

units but only one zone sensor) for both standalone (with communica-

tion wiring between units) and building automation system applica-

tions. For this application you will need to use the Rover service tool.

For more information on setup, refer to the Trane publication EMTX-

IOP-2.

The Tracer

®

ZN.520 controller has four available binary inputs. Nor-

mally, these inputs are factory-configured for the following functions:

• Binary input 1: Low temperature detection (freezestat)

• Binary input 2: Condensate overflow

• Binary input 3: Occupancy/ Generic

• Binary input 4: Fan status

Note: The generic binary input can be used with a Tracer Summit

®

building automation system only.

Each binary input default configuration (including normally open/

closed) is set at the factory.However, you can configure each of the

four binary inputs as normally open or normally closed. The controller

will be set properly for each factory-supplied binary input end-device.

When no device is connected to the input, configure the controller’s

Dehumidification

Data Sharing

Binary Inputs