UNT-IOM-6

95

Terminal Unit
Control (TUC)

Note: The auxiliary electric heat option is not available with a four-pipe

fan-coil unit.

Units with manual fresh air

dampers ship with the damper in

the closed position, which is

adjustable from zero to 100

percent in 25 percent incre-

ments. To adjust the position,

first remove the air filter to

expose the damper stop screw

on the control panel end. Relo-

cate the stop screw to the

appropriate position. Then loosen

the stop screw wingnut and

adjust the linkage. See Figure

30.

Units with an auto 2-position fresh air damper ship with a stop screw

in the 25 percent reference position. The auto damper is adjustable to

open from zero to 50 percent in 25 percent increments. To adjust the

damper position, remove the air filter to expose the damper stop

screw on the control panel end. Then relocate the stop screw to the

appropriate position. See Figure 30.

Note: The open position of the damper does not correspond to the

amount of fresh air. It is the installer’s responsibility to ensure that

the building’s minimum fresh air requirements are met while taking

necessary precautions to protect the unit during freeze conditions.

The economizer damper option contains a modulating, 3-wire floating

point actuator and a damper assembly. The factory sets the damper

at a minimum 25 percent open position by configuring the TUC. This

setting is adjustable and can be changed in the field with EveryWareä

software or Tracer

â

. The minimum open position is adjustable from

zero to 100 percent in one percent increments.

The economizer fresh air damper is controlled to the minimum

position, which the factory configures. During the occupied mode,

economizing is enabled and the fresh air temperature is measured

while economizing.

Economizing is enabled within the TUC configuration based on an

editable temperature differential between the fresh air temperature and

the zone temperature. The unit will go into economizing mode when

Fresh Air Damper
Options

Auto 2-Position

Economizer

Figure 30. Re-locate the damper
stop screw to adjust the damper
position. The factory positions
the stop screw in the 25% open
position.

Manual