Fan mode operation 93, Terminal unit control (tuc), Fan mode operation – Trane LO User Manual

Page 93

background image

UNT-IOM-6

93

Terminal Unit
Control (TUC)

high or low temperatures. In addition, the TUC calculates the heating

setpoint equal to the cooling setpoint minus an adjustable heating

offset. Furthermore, the heating setpoint cannot exceed a value less

than or equal to the cooling setpoint. The TUC is in the cooling mode

when the space temperature rises 1° F above the cooling setpoint.

The TUC is in the heating mode when the space temperature drops 1°

F below the heating setpoint. The unoccupied setpoints are typically

widened to account for night setback and are adjustable with either

Tracer

®

or EveryWareä software.

Off Position

On a stand-alone TUC with the fan mode switch in the off position, all

normal cooling and heating functions cease. (e.g. The fan does not

run, the fresh air damper option closes, and the unoccupied mode

disables.)

High, Medium, or Low Postion

With the fan mode switch in the high, medium, or low position; the

fresh air damper option and the control valve(s) operate to maintain

setpoint.

Auto Position

As the capacity requirement increases at low fan speed, the control

valve gradually opens. The fan speed increases to medium after

reaching the low speed capacity switch point. This causes the control

valve to reposition to maintain capacity, gradually opening as demand

increases. The fan speed increases to high after reaching the medium

speed capacity switch point. This causes the control valve to reposi-

tion to maintain output capacity, gradually opening as demand

increases. As capacity decreases, the control valve closes until

reaching the fan switch point. After reaching the fan switch point, the

fan speed decreases to medium with the control valve repositioning to

maintain constant capacity. As capacity decreases, the control valve

closes until reaching the fan switch point. After reaching the fan

switch point, the fan speed decreases to low with the control valve

repositioning to maintain constant capacity. At low speed, the control

valve closes incrementally as demand decreases.

Fan Mode
Operation