Terminal Unit
Control (TUC)

108

UNT-IOM-6

Remove the 24 VAC power from the board and then reapply it to

cycle the unit through a power-up sequence. By default, the controller

attempts to reset all diagnostics at power-up.

The TUC editor’s reset failure point allows the user to reset controller

diagnostics. Also, Tracer

®

versions 14.4 and higher provide a “+

enter” option from the TUC service summary screens that allow

latching diagnostic reset.

When using a Tracer Summit

®

system, reset the unit diagnostics with

the reset diagnostics button on the TUC editor screen.

The unit’s operating machine state is in standby when one of the

following conditions occurs:

1. Tracer

®

override is present.

2. During the power-up sequence or any time when the TUC is

calibrating its end devices.

3. When the TUC is in the unoccupied mode and there is no call for

heating or cooling.

4. In the occupied mode when the desired capacity is unavailable.

ie: the TUC requests a 2-pipe unit to heat, yet no hot water or electric

heat is available. The TUC will list the unit as being in standby mode.

Unit Mode Listed
as Standby

Cycling Power to the
TUC

Using Tracer 100i

or

100L

Using Tracer Summit

®