beautypg.com

Terminal unit control (tuc) – Trane LO User Manual

Page 112

background image

Terminal Unit
Control (TUC)

112

UNT-IOM-6

Table 48. Electric Heat Not Operating
Probable Cause

Explanation

Normal Operation

The controller cycles electric heat on and off to meet the unit

capacity requirements.

Unit Disabled

The TUC may be disabled via the shutdown mode on a Tracer

®

system or if BIP1 is configured as external interlock.

Electric Heat Control: Disable

The electric heat may be disabled with the Tracer

®

system. To

enable the electric heat, the TUC electric heat control must be set

to the auto postion.

Maximum heating capacity of zero The Tracer

®

may limit the maximum heating/cooling capacity of the

TUC from zero to 100%. When the maximum heating capacity is

zero, the electric heat is disabled.

Latching Diagnostic Present

A specific list of diagnostics affects electric heat operation. For

more information, see the “Diagnostics” section on page 73.

Latching diagnostics require a manual reset to restore normal unit

operation.

Autocycle Test

The controller includes an autocycle test sequence that verifies

analog and binary output operation and associated output wiring.

However, based on the current stage in the test sequence, the

electric heat may be disabled. Refer to the “Autocycle Test”

section on page 71.

Unit Configuration

The TUC cannot control the electric heat output if the unit is config-

ured for no electric heat. Also, if the electric heat type is incorrectly

configured (1 or 2 stage), the electric heat may not operate prop-

erly.

No Power to the TUC

The TUC requires 24 VAC power for the unit to operate properly.

Wiring

The wiring between the controller outputs and the electric heat must

be present and correct for normal electric heat operation. Refer to

the typical unit wiring diagrams on pages 105-106.