beautypg.com

Maintenance procedures 116, Periodic maintenance check, List 116 – Trane LO User Manual

Page 116: Maintenance 116, Maintenance, Periodic maintenance checklist, Maintenance procedures

background image

116

UNT-IOM-6

Listed below are the recommended maintenance schedules. Instruc-

tions for specific maintenance procedures are given in the sections

following the checklist.

WARNING: Allow rotating fan to stop before

servicing equipment. Failure to do so may cause severe
personal injury or death.

Monthly

1. Inspect the unit air filters. Clean or replace dirty filters.

Note: Building conditions may require filter change more or less

frequently.

2. Check the main and auxiliary drain pans on fan-coil units to be

sure the pans are clean and do not impede the condensate flow

through the drain line.

Yearly

1. Inspect the unit cabinetry for chips or corrosion. Clean or repair to

provide unit protection.

2. Inspect the fan wheel and housing for damage. Rotate the fan

wheel manually to be sure movement is not blocked by obstructions.

3. Inspect the coil fins for excessive dirt or damage. Remove dirt and

straighten fins.

4. Clean and tighten all electrical connections.

5. Inspect the strainer option for debris trapped in the filter screen.

Change or clean air filters at least twice a year. Filters require more

frequent care under high load or dirty air conditions since a clogged

filter reduces airflow. Table 37 on page 89 lists filter sizes for units.

Throwaway and pleated media filters are available for all units. Follow

the instructions below to replace the disposable filters.

1. All models except vertical cabinets

Remove the front panel of the vertical recessed unit and open the

bottom panel door of the horizontal cabinet and horizontal recessed

unit to access the filter. The front panel of the vertical cabinet unit

does not require removal to change the filter.

Maintenance

Periodic
Maintenance
Checklist

!

Maintenance
Procedures

Filters