beautypg.com

Yellow comm led 47, Tracer, Yellow comm led – Trane LO User Manual

Page 47

background image

UNT-IOM-6

47

Tracer

®

ZN.010

and ZN.510

Table 12. Yellow COMM LED Activity
Yellow LED Blink Activity

Description

LED off continuously

The controller is not detecting any communication.

(Normal for units in standalone applications)

LED blinks

The controller detects communication.

LED on continuously

Abnormal condition

Table 11. Green STATUS LED Activity
Green LED Blink Activity

Description

LED on continuously

Power on (normal operation)

LED blinks once

Manual output test mode

LED blinks twice

Manual output test mode, with one or more diagnos-

tic present

LED blinks (1/4 second on, 1/4 second

off for 10 seconds)

“Wink” mode

LED off

· Power off

· Abnormal condition

· Test button is pressed

Green STATUS LED

Note: The “wink” feature allows the identification of a particular controller. When sending a request from a

device, such as Rover™, the controller will “wink” to indicate it received the signal.

Yellow COMM LED

The green LED normally indicates whether the controller is powered

on (24 VAC supplied). Reference Table 11.