beautypg.com

Tuc human interface 90, Terminal unit control (tuc), Tuc human interface – Trane LO User Manual

Page 90

background image

Terminal Unit
Control (TUC)

90

UNT-IOM-6

3. Rotate the setpoint dial on the zone sensor module to 55° F for

cooling or 85° F for heating.

The appropriate control valve will actuate assuming the following

conditions:

· Room temperature should be greater than 55° F and less

than 85° F

· For a 2-pipe fan-coil unit with an automatic changeover

sensor, the water temperature input is appropriate for the

demand placed on the unit, e.g. cooling operation is re-

quested and cold water (5° F lower than room temperature

for a TUC) flows into the unit.

4. Select the correct temperature setpoint.

Note: Select and enable zone sensor temperature settings to prevent

freeze damage to unit.

TUCs connected to a Tracer

®

comm 4 communication link requires a

unique address. Use the TUC’s eight DIP switches to set the ICS

address. The address must be in the valid range of 33 to 96. See

Table 21 on page 63 for address settings.

To set the ICS address, perform the following steps:

1. Set the DIP switches to the correct address. ON implies that the

DIP switch is pressed towards the DIP switch number. OFF implies

that the DIP switch is pressed towards the OPEN position.

2. Short and hold the test input (J11 and J12) until all LEDs are

illuminated. Remove the jumper from the test input. This sets the

address in the TUC EEPROM.

Note: Cycling power to the TUC forces the TUC to read the DIP

switch settings (Rev 12 TUC or higher). The TUC firmware version

can be read from either Tracer or Everyware. Additionally, the last two

digits of the part number printed on the sticker on the TUC 1U1

microprocessor indicate the TUC firmware version, ie: 6200-0028-13.

The TUC operates the fan in the following modes:

Setting the ICS Ad-
dress for Tracer Com-
munications

TUC Human
Interface