The unit’s airflow configuration varies dependent on the model and

options ordered. A one-inch duct collar is provided on units with a

ducted return and/or discharge to attach ductwork to the unit.

The Trane Company recommends using galvanized sheet metal

ductwork with fan-coil and cabinet heater units. Slide the sheetmetal

duct over the duct collar flange of the unit, seal the joint and fasten

with sheetmetal screws.

Note: Do not run screws through the removable front panel on con-

cealed units.

Install all air ducts according to National Fire Protection Association

standards for the Installation of Air Conditioning and Ventilating

Systems (NFPA 90A and 90B).

Follow the general recommendations listed below when installing

ductwork for the unit.

· Discharge ductwork should run in a straight line, unchanged in size

or direction, for a minimum equivalent distance of 3 fan diameters

from the unit (approximately 20 inches).

· When making duct turns and transitions avoid sharp turns and use

proportional splits, turning vanes, and air scoops when necessary.

· When possible, construct, and orient supply ductwork turns in the

same direction as the fan rotation.