Using the human interface, read the operating control mode.

1. Read and record the initial TUC address.

2. Set the TUC DIP switch #5 and #7 to ON (address = 10). The

remaining switches will be off.

3. Short and hold the test input.

4. The LEDs will blink to define an operating control mode. The

operating control mode information will be displayed in a series of

three blink sequences.

Sequence 1: With the test input shorted continuously, all

LEDs go off for one second.

Sequence 2: LED #5 will light to indicate that sequence 2 is

currently displayed. LEDs one through four

will display the first part of the operating control

mode.

Sequence 3: LED #6 will light to indicate that sequence 3 is

currently being displayed. LEDs one through four

will display the second part of the operating control

mode.

5. Refer to Table 26 on page 77 to interpret the operating control

mode derived from the blink sequences.

6. After reading and recording the operating control mode, return the

DIP switches to the positions recorded in step 1. Short the test

inputs to set the address in the TUC EEPROM.