beautypg.com

Performance data system – Trane SS-PRC003-EN User Manual

Page 28

background image

28

SS-PRC003-EN

Performance
Data

System

Table PD-15 — Gross Cooling Capacities (MBh)

TTA200B Condensing Unit with TWE200B Air Handler

(I-P)

Ambient Temperature (°F)

85

95

105

115

Enter.
Dry

Entering Wet Bulb (°F)

CFM

Bulb

61

67

73

61

67

73

61

67

73

61

67

73

Airflow

(°F)

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

75

203.5

160.6 224.5 134.3 247.0 91.4

195.8

156.6 215.9 130.8 237.4 88.1 187.6 152.4 207.0 127.2 227.3 84.6 179.2 148.2 197.8 123.5 216.6 81.0

6000

80

204.7

187.3 224.9 154.7 247.8 120.1

197.2

183.4 216.5 150.8 238.4 116.6 189.3 179.4 207.7 146.8 228.7 113.0 181.1 175.3 198.6 142.6 218.6 109.2

85

209.3

209.3 226.0 181.2 248.8 148.0

202.9

202.9 217.6 177.4 239.4 144.5 196.1 196.1 208.8 173.4 229.8 140.8 189.0 189.0 199.7 169.2 219.8 137.2

90

220.0

220.0 227.3 208.2 249.1 174.6

213.4

213.4 219.1 204.4 239.8 170.9 206.5 206.5 210.7 200.5 230.3 167.0 199.3 199.3 202.0 196.5 220.4 162.9

75

207.6

168.0 228.8 132.3 250.9 93.0

199.6

164.0 219.9 128.6 240.9 89.6 191.2 159.7 210.7 124.8 230.5 86.0 182.5 155.4 201.2 121.0 219.8 82.4

6675

80

209.3

197.5 229.3 161.5 252.0 124.2

201.6

193.5 220.5 157.5 242.3 120.6 193.6 189.5 211.4 153.4 232.3 117.0 185.4 185.3 202.1 149.2 221.9 113.2

85

216.3

216.3 230.4 190.6 253.1 154.7

209.6

209.6 221.6 186.6 243.5 151.1 202.4 202.4 212.6 182.6 232.8 146.5 195.0 195.0 203.3 178.4 222.5 142.3

90

227.5

227.5 232.3 220.2 253.6 183.3

220.6

220.6 224.0 216.4 244.0 179.4 213.3 213.3 215.4 212.5 234.1 175.5 205.7 205.7 205.9 205.9 223.9 171.4

75

211.1

175.1 232.2 136.8 254.0 94.7

202.8

171.0 223.1 133.1 243.7 91.2 194.2 166.7 213.7 129.3 233.2 87.5 185.3 162.3 203.0 124.3 222.2 83.7

7350

80

213.4

207.2 232.9 168.0 255.5 128.1

205.6

203.3 223.9 163.9 245.5 124.5 196.9 196.9 214.6 159.8 235.3 120.8 189.3 189.3 205.0 155.5 224.6 117.0

85

222.4

222.4 234.0 199.5 256.7 161.0

215.4

215.4 225.1 195.5 246.1 156.2 208.0 208.0 216.0 191.4 236.0 152.2 200.3 200.3 206.5 187.2 225.5 148.0

90

234.1

234.1 236.9 231.9 257.3 191.6

226.8

226.8 228.5 228.1 247.5 187.7 219.2 219.2 219.5 219.5 237.3 183.6 211.3 211.3 211.5 211.5 226.9 179.5

75

214.1

181.9 235.2 141.1 256.7 96.2

205.6

177.7 225.8 137.3 246.2 92.5 196.8 173.4 215.4 132.3 235.3 88.7 187.8 168.9 205.5 127.9 224.1 84.8

8025

80

217.3

216.7 236.0 174.2 258.5 131.8

208.9

208.9 226.8 170.1 248.3 128.1 201.4 201.4 217.3 165.8 237.8 124.4 193.6 193.6 207.5 161.5 226.9 120.6

85

227.9

227.9 237.3 208.1 259.2 165.7

220.6

220.6 228.3 204.1 249.1 161.8 212.9 212.9 218.9 200.0 238.7 157.7 204.9 204.9 209.4 195.7 228.0 153.4

90

239.9

239.9 240.1 240.1 260.5 199.6

232.4

232.4 232.6 232.6 250.4 195.6 224.5 224.5 224.7 224.7 240.1 191.5 216.3 216.3 216.5 216.5 229.4 187.3

Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.

All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity

Table PD-15 — Gross Cooling Capacities (MBh)

TTA200B Condensing Unit with TWE200B Air Handler

(SI)

Ambient Temperature (°C)

29.4

35.0

40.6

46.1

Enter.
Dry

Entering Wet Bulb (°C)

m

3

/h

Bulb

16.1

19.4

22.8

16.1

19.4

22.8

16.1

19.4

22.8

16.1

19.4

22.8

Airflow

(°C)

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

24

59.6

47.0

65.7

39.3

72.3

26.8

57.3

45.8

63.2

38.3

69.5

25.8

54.9

44.6

60.6

37.3

66.5

24.8

52.5

43.4

57.9

36.2

63.4

23.7

10194

27

59.9

54.8

65.9

45.3

72.5

35.2

57.7

53.7

63.4

44.2

69.8

34.1

55.4

52.5

60.8

43.0

67.0

33.1

53.0

51.3

58.1

41.8

64.0

32.0

29

61.3

61.3

66.2

53.1

72.8

43.3

59.4

59.4

63.7

51.9

70.1

42.3

57.4

57.4

61.1

50.8

67.3

41.2

55.3

55.3

58.5

49.6

64.3

40.2

32

64.4

64.4

66.6

61.0

72.9

51.1

62.5

62.5

64.2

59.8

70.2

50.0

60.5

60.5

61.7

58.7

67.4

48.9

58.3

58.3

59.1

57.5

64.5

47.7

24

60.8

49.2

67.0

38.7

73.5

27.2

58.4

48.0

64.4

37.7

70.5

26.2

56.0

46.8

61.7

36.6

67.5

25.2

53.4

45.5

58.9

35.4

64.3

24.1

11341

27

61.3

57.8

67.1

47.3

73.8

36.4

59.0

56.7

64.6

46.1

71.0

35.3

56.7

55.5

61.9

44.9

68.0

34.2

54.3

54.3

59.2

43.7

65.0

33.2

29

63.3

63.3

67.5

55.8

74.1

45.3

61.4

61.4

64.9

54.6

71.3

44.2

59.3

59.3

62.2

53.5

68.2

42.9

57.1

57.1

59.5

52.2

65.2

41.7

32

66.6

66.6

68.0

64.5

74.2

53.7

64.6

64.6

65.6

63.4

71.5

52.5

62.4

62.4

63.1

62.2

68.6

51.4

60.2

60.2

60.3

60.3

65.6

50.2

24

61.8

51.3

68.0

40.1

74.4

27.7

59.4

50.1

65.3

39.0

71.4

26.7

56.9

48.8

62.6

37.8

68.3

25.6

54.3

47.5

59.4

36.4

65.0

24.5

12488

27

62.5

60.7

68.2

49.2

74.8

37.5

60.2

59.5

65.6

48.0

71.9

36.4

57.6

57.6

62.8

46.8

68.9

35.4

55.4

55.4

60.0

45.5

65.8

34.3

29

65.1

65.1

68.5

58.4

75.2

47.1

63.1

63.1

65.9

57.2

72.1

45.7

60.9

60.9

63.2

56.0

69.1

44.6

58.6

58.6

60.5

54.8

66.0

43.3

32

68.5

68.5

69.4

67.9

75.3

56.1

66.4

66.4

66.9

66.8

72.5

55.0

64.2

64.2

64.3

64.3

69.5

53.8

61.9

61.9

61.9

61.9

66.4

52.6

24

62.7

53.3

68.9

41.3

75.2

28.2

60.2

52.0

66.1

40.2

72.1

27.1

57.6

50.8

63.1

38.7

68.9

26.0

55.0

49.5

60.2

37.5

65.6

24.8

13634

27

63.6

63.5

69.1

51.0

75.7

38.6

61.2

61.2

66.4

49.8

72.7

37.5

59.0

59.0

63.6

48.6

69.6

36.4

56.7

56.7

60.7

47.3

66.4

35.3

29

66.7

66.7

69.5

60.9

75.9

48.5

64.6

64.6

66.8

59.8

72.9

47.4

62.3

62.3

64.1

58.6

69.9

46.2

60.0

60.0

61.3

57.3

66.8

44.9

32

70.2

70.2

70.3

70.3

76.3

58.4

68.0

68.0

68.1

68.1

73.3

57.3

65.7

65.7

65.8

65.8

70.3

56.1

63.3

63.3

63.4

63.4

67.2

54.9

Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.

All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity