Performance data system – Trane SS-PRC003-EN User Manual

Page 22

background image

22

SS-PRC003-EN

Performance
Data

System

Table PD-9 — Gross Cooling Capacities (MBh)

TTA125B Condensing Unit with TWE100B Air Handler

(I-P)

Ambient Temperature (°F)

85

95

105

115

Enter.
Dry

Entering Wet Bulb (°F)

CFM

Bulb

61

67

73

61

67

73

61

67

73

61

67

73

Airflow

(°F)

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

75

109.9

81.1 121.9 71.0 135.2 49.8

106.3

79.2 117.8 69.3 130.6 48.0 102.0 76.9 113.3 67.5 125.5 46.3

97.6

74.6 108.5 65.5 120.2 44.3

3025

80

110.2

92.5 122.2 78.4 135.2 63.2

106.5

90.6 118.1 76.5 130.6 61.3 102.5 88.4 113.7 74.5 125.6 59.3

98.1

86.1 108.9 72.3 120.2 57.1

85

110.6

104.2 122.5 90.4 135.4 75.2

107.1

102.3 118.2 88.3 130.8 73.3 103.3 100.2 113.8 86.1 125.9 71.3

99.2

98.0 109.1 83.8 120.6 69.2

90

113.5

113.5 122.7 101.8 135.7 87.3

110.5

110.5 118.6 99.8 131.1 85.4 107.3 107.3 114.2 97.7 126.2 83.3 103.6 103.6 109.5 95.4 120.9 81.2

75

112.6

84.5 124.7 68.5 138.0 50.8

108.5

82.3 120.4 66.6 133.2 49.1 104.3 80.0 115.7 64.5 127.9 47.2

99.8

77.7 110.7 62.3 122.3 45.3

3350

80

112.8

96.8 125.0 81.5 138.0 65.0

109.0

94.7 120.7 79.6 133.2 63.0 104.8 92.5 116.1 77.5 128.0 61.0 100.3 90.1 111.1 75.3 122.4 58.8

85

113.6

109.5 125.1 94.2 138.3 78.0

110.0

107.6 120.8 92.1 133.5 76.1 106.1 105.5 116.3 90.0 128.3 74.1 101.8 101.8 111.4 87.6 122.8 71.9

90

117.6

117.6 125.5 106.7 138.6 91.1

114.5

114.5 121.3 104.6 133.8 89.1 111.0 111.0 116.7 102.5 128.7 87.1 107.2 107.2 111.8 100.1 123.2 84.9

75

114.6

87.3 127.0 70.4 140.3 51.8

110.7

85.3 122.5 68.5 135.3 50.0 106.4 83.0 117.7 66.4 129.9 48.2 101.6 80.6 112.5 64.1 124.1 46.2

3675

80

115.1

100.8 127.3 84.5 140.3 66.6

111.2

98.7 122.9 82.5 135.4 64.7 106.9 96.4 118.1 80.4 130.0 62.6 102.1 94.0 113.0 78.1 124.3 60.4

85

116.3

114.6 127.5 97.9 140.6 80.7

112.2

112.2 123.1 95.8 135.7 78.7 108.7 108.7 118.4 93.6 130.4 76.6 104.8 104.8 113.3 91.2 124.7 74.5

90

121.3

121.3 127.9 111.3 141.0 94.7

117.9

117.9 123.5 109.2 136.1 92.7 114.3 114.3 118.8 107.0 130.5 90.3 110.4 110.4 113.8 104.7 124.9 87.9

75

116.6

90.2 129.0 72.3 142.3 52.7

112.5

88.1 124.4 70.3 137.1 51.0 108.1 85.8 119.4 68.1 131.5 49.1 103.2 83.3 114.1 65.9 125.6 46.9

4000

80

117.1

104.5 129.4 87.2 142.3 68.2

113.0

102.4 124.8 85.2 137.3 66.2 108.6 100.2 119.6 82.7 131.8 64.1 103.9 97.7 114.4 80.3 125.9 61.9

85

118.5

118.5 129.6 101.4 142.7 83.2

115.1

115.1 125.1 99.3 137.7 81.2 111.5 111.5 120.2 97.0 132.2 79.1 107.5 107.5 114.9 94.6 126.4 76.9

90

124.5

124.5 130.0 115.8 143.1 98.1

121.1

121.1 125.5 113.7 137.8 95.7 117.3 117.3 120.7 111.4 132.4 93.5 113.2 113.2 115.6 109.1 126.6 91.1

Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.

All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity

Table PD-9 — Gross Cooling Capacities (kW)

TTA125B Condensing Unit with TWE100B Air Handler

(SI)

Ambient Temperature (°C)

29.4

35.0

40.6

46.1

Enter.
Dry

Entering Wet Bulb (°C)

m

3

/h

Bulb

16.1

19.4

22.8

16.1

19.4

22.8

16.1

19.4

22.8

16.1

19.4

22.8

Airflow

(°C)

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

24

32.2

23.7

35.7

20.8

39.6

14.6

31.1

23.2

34.5

20.3

38.2

14.1

29.9

22.5

33.2

19.8

36.8

13.6

28.6

21.8

31.8

19.2

35.2

13.0

5139

27

32.3

27.1

35.8

23.0

39.6

18.5

31.2

26.5

34.6

22.4

38.2

17.9

30.0

25.9

33.3

21.8

36.8

17.4

28.7

25.2

31.9

21.2

35.2

16.7

29

32.4

30.5

35.9

26.5

39.6

22.0

31.4

29.9

34.6

25.8

38.3

21.5

30.2

29.3

33.3

25.2

36.9

20.9

29.0

28.7

31.9

24.6

35.3

20.3

32

33.2

33.2

35.9

29.8

39.7

25.5

32.4

32.4

34.7

29.2

38.4

25.0

31.4

31.4

33.5

28.6

36.9

24.4

30.3

30.3

32.1

27.9

35.4

23.8

24

33.0

24.7

36.5

20.1

40.4

14.9

31.8

24.1

35.2

19.5

39.0

14.4

30.5

23.4

33.9

18.9

37.5

13.8

29.2

22.7

32.4

18.2

35.8

13.3

5692

27

33.0

28.3

36.6

23.9

40.4

19.0

31.9

27.7

35.3

23.3

39.0

18.5

30.7

27.1

34.0

22.7

37.5

17.9

29.4

26.4

32.5

22.1

35.9

17.2

29

33.3

32.1

36.6

27.6

40.5

22.8

32.2

31.5

35.4

27.0

39.1

22.3

31.1

30.9

34.0

26.3

37.6

21.7

29.8

29.8

32.6

25.7

36.0

21.1

32

34.4

34.4

36.8

31.2

40.6

26.7

33.5

33.5

35.5

30.6

39.2

26.1

32.5

32.5

34.2

30.0

37.7

25.5

31.4

31.4

32.7

29.3

36.1

24.9

24

33.6

25.6

37.2

20.6

41.1

15.2

32.4

25.0

35.9

20.0

39.6

14.7

31.1

24.3

34.5

19.4

38.0

14.1

29.8

23.6

32.9

18.8

36.3

13.5

6244

27

33.7

29.5

37.3

24.7

41.1

19.5

32.5

28.9

36.0

24.1

39.6

18.9

31.3

28.2

34.6

23.5

38.1

18.3

29.9

27.5

33.1

22.9

36.4

17.7

29

34.0

33.6

37.3

28.7

41.2

23.6

32.8

32.8

36.0

28.0

39.7

23.0

31.8

31.8

34.7

27.4

38.2

22.4

30.7

30.7

33.2

26.7

36.5

21.8

32

35.5

35.5

37.5

32.6

41.3

27.7

34.5

34.5

36.2

32.0

39.8

27.1

33.5

33.5

34.8

31.3

38.2

26.4

32.3

32.3

33.3

30.7

36.6

25.7

24

34.1

26.4

37.8

21.2

41.7

15.4

32.9

25.8

36.4

20.6

40.2

14.9

31.7

25.1

35.0

19.9

38.5

14.4

30.2

24.4

33.4

19.3

36.8

13.7

6796

27

34.3

30.6

37.9

25.5

41.7

20.0

33.1

30.0

36.5

25.0

40.2

19.4

31.8

29.3

35.0

24.2

38.6

18.8

30.4

28.6

33.5

23.5

36.9

18.1

29

34.7

34.7

38.0

29.7

41.8

24.3

33.7

33.7

36.6

29.1

40.3

23.8

32.6

32.6

35.2

28.4

38.7

23.2

31.5

31.5

33.7

27.7

37.0

22.5

32

36.5

36.5

38.1

33.9

41.9

28.7

35.4

35.4

36.7

33.3

40.3

28.0

34.3

34.3

35.3

32.6

38.8

27.4

33.1

33.1

33.9

31.9

37.1

26.7

Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.

All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity