Performance data system – Trane SS-PRC003-EN User Manual

Page 18

background image

18

SS-PRC003-EN

Table PD-5 — Gross Cooling Capacities (MBh) TTA100A Condensing Unit with TWE100A Air Handler

(I-P)

Ambient Temperature (°F)

85

95

105

115

Enter.
Dry

Entering Wet Bulb (°F)

CFM

Bulb

61

67

73

61

67

73

61

67

73

61

67

73

Airflow

(°F)

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

75

104.7

81.7 115.8 68.5 127.7 46.8

100.9

79.7 111.5 66.8 123.0 45.1

96.8

77.7 107.1 65.0 118.1 43.5

92.4

75.5 102.5 63.2 112.9 41.7

3025

80

105.2

95.0 116.1 78.6 127.8 61.1

101.5

93.1 111.9 76.8 123.2 59.3

97.5

91.1 107.5 75.0 118.3 57.5

93.3

89.0 102.9 73.0 113.3 55.6

85

106.9

106.9 116.3 92.0 128.1 74.9

103.8

103.8 112.1 90.1 123.5 73.1 100.4 100.4 107.7 88.1 118.7 71.3

96.9

96.9 103.1 86.1 113.7 69.5

90

112.3

112.3 116.8 105.4 128.4 88.7

109.1

109.1 112.7 103.5 123.8 86.9 105.7 105.7 108.4 101.6 119.0 85.1 102.1 102.1 104.1 99.7 113.8 82.9

75

106.8

85.3 118.0 67.1 129.8 47.6

102.8

83.3 113.6 65.3 124.9 46.0

98.6

81.2 109.0 63.4 119.8 44.2

94.2

79.1 104.3 61.5 114.5 42.4

3350

80

107.5

99.9 118.3 82.1 130.0 63.0

103.7

98.0 113.9 80.3 125.2 61.2

99.6

96.0 109.4 78.4 120.2 59.4

95.4

93.9 104.5 76.0 115.0 57.5

85

110.4

110.4 118.4 96.5 130.3 78.1

107.1

107.1 114.1 94.6 125.5 76.3 103.7 103.7 109.6 92.6 120.6 74.5 100.0 100.0 104.9 90.5 115.4 72.6

90

116.1

116.1 119.2 111.2 130.5 93.1

112.7

112.7 115.0 109.3 125.6 90.9 109.1 109.1 110.7 107.4 120.7 89.0 105.4 105.4 106.3 105.4 115.6 87.0

75

108.6

88.8 119.7 69.3 131.5 48.5

104.5

86.8 115.2 67.4 126.5 46.8 100.2 84.7 110.6 65.5 121.2 44.9

95.6

82.4 105.7 63.5 115.8 43.0

3675

80

109.5

104.7 120.1 85.4 131.7 64.8

105.6

102.7 115.4 83.2 126.8 63.1 101.6 100.7 110.8 81.2 121.7 61.2

97.0

97.0 105.9 79.1 116.4 59.3

85

113.5

113.5 120.3 100.8 132.1 81.1

110.1

110.1 115.8 98.8 127.2 79.3 106.4 106.4 111.2 96.8 122.1 77.5 102.6 102.6 106.5 94.8 116.8 75.6

90

119.4

119.4 121.4 116.8 132.2 96.8

115.8

115.8 117.2 114.9 127.3 94.9 112.1 112.1 112.2 112.2 122.3 92.9 108.2 108.2 108.3 108.3 117.0 90.9

75

110.1

92.1 121.2 71.3 132.9 49.2

105.9

90.0 116.6 69.4 127.8 47.4 101.5 87.9 111.9 67.5 122.4 45.5

96.9

85.7 106.9 65.6 116.8 43.6

4000

80

111.4

109.2 121.4 88.2 133.2 66.6

107.5

107.3 116.9 86.2 128.2 64.8 103.1 103.1 112.1 84.2 123.0 63.0

99.3

99.3 107.2 82.0 117.6 61.1

85

116.3

116.3 121.9 105.0 133.6 84.0

112.7

112.7 117.4 103.0 128.6 82.2 108.9 108.9 112.7 101.0 123.4 80.4 105.0 105.0 107.9 98.9 117.8 78.0

90

122.3

122.3 123.5 122.3 133.8 100.7

118.6

118.6 118.7 118.7 128.8 98.7 114.7 114.7 114.8 114.8 123.7 96.8 110.7 110.7 110.8 110.8 118.3 94.7

Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.

All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity

Table PD-5 — Gross Cooling Capacities (kW) TTA100A Condensing Unit with TWE100A Air Handler

(SI)

Ambient Temperature (°C)

29.4

35.0

40.6

46.1

Enter.
Dry

Entering Wet Bulb (°C)

m

3

/h

Bulb

16.1

19.4

22.8

16.1

19.4

22.8

16.1

19.4

22.8

16.1

19.4

22.8

Airflow

(°C)

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

24

30.7

23.9

33.9

20.1

37.4

13.7

29.5

23.3

32.7

19.6

36.0

13.2

28.3

22.7

31.4

19.0

34.6

12.7

27.1

22.1

30.0

18.5

33.1

12.2

5139

27

30.8

27.8

34.0

23.0

37.4

17.9

29.7

27.3

32.8

22.5

36.1

17.4

28.5

26.7

31.5

22.0

34.6

16.8

27.3

26.1

30.1

21.4

33.2

16.3

29

31.3

31.3

34.0

26.9

37.5

21.9

30.4

30.4

32.8

26.4

36.2

21.4

29.4

29.4

31.5

25.8

34.7

20.9

28.4

28.4

30.2

25.2

33.3

20.3

32

32.9

32.9

34.2

30.9

37.6

26.0

31.9

31.9

33.0

30.3

36.2

25.5

30.9

30.9

31.8

29.8

34.8

24.9

29.9

29.9

30.5

29.2

33.3

24.3

24

31.3

25.0

34.5

19.7

38.0

13.9

30.1

24.4

33.3

19.1

36.6

13.5

28.9

23.8

31.9

18.6

35.1

12.9

27.6

23.1

30.5

18.0

33.5

12.4

5692

27

31.5

29.3

34.6

24.0

38.1

18.5

30.3

28.7

33.4

23.5

36.7

17.9

29.2

28.1

32.0

23.0

35.2

17.4

27.9

27.5

30.6

22.3

33.7

16.8

29

32.3

32.3

34.7

28.3

38.1

22.9

31.4

31.4

33.4

27.7

36.8

22.3

30.3

30.3

32.1

27.1

35.3

21.8

29.3

29.3

30.7

26.5

33.8

21.3

32

34.0

34.0

34.9

32.6

38.2

27.2

33.0

33.0

33.7

32.0

36.8

26.6

31.9

31.9

32.4

31.4

35.3

26.1

30.9

30.9

31.1

30.9

33.8

25.5

24

31.8

26.0

35.1

20.3

38.5

14.2

30.6

25.4

33.7

19.7

37.0

13.7

29.3

24.8

32.4

19.2

35.5

13.2

28.0

24.1

30.9

18.6

33.9

12.6

6244

27

32.1

30.6

35.2

25.0

38.6

19.0

30.9

30.1

33.8

24.4

37.1

18.5

29.7

29.5

32.4

23.8

35.6

17.9

28.4

28.4

31.0

23.2

34.1

17.4

29

33.2

33.2

35.2

29.5

38.7

23.7

32.2

32.2

33.9

28.9

37.2

23.2

31.2

31.2

32.6

28.4

35.8

22.7

30.0

30.0

31.2

27.8

34.2

22.1

32

35.0

35.0

35.6

34.2

38.7

28.3

33.9

33.9

34.3

33.7

37.3

27.8

32.8

32.8

32.8

32.8

35.8

27.2

31.7

31.7

31.7

31.7

34.3

26.6

24

32.2

27.0

35.5

20.9

38.9

14.4

31.0

26.4

34.2

20.3

37.4

13.9

29.7

25.7

32.8

19.8

35.8

13.3

28.4

25.1

31.3

19.2

34.2

12.8

6796

27

32.6

32.0

35.6

25.8

39.0

19.5

31.5

31.4

34.2

25.2

37.5

19.0

30.2

30.2

32.8

24.6

36.0

18.4

29.1

29.1

31.4

24.0

34.4

17.9

29

34.0

34.0

35.7

30.7

39.1

24.6

33.0

33.0

34.4

30.2

37.7

24.1

31.9

31.9

33.0

29.6

36.1

23.5

30.7

30.7

31.6

29.0

34.5

22.8

32

35.8

35.8

36.2

35.8

39.2

29.5

34.7

34.7

34.8

34.8

37.7

28.9

33.6

33.6

33.6

33.6

36.2

28.3

32.4

32.4

32.4

32.4

34.6

27.7

Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity