beautypg.com

General data, General data condensing unit – Trane SS-PRC003-EN User Manual

Page 11

background image

11

SS-PRC003-EN

General
Data

Condensing Unit

Table GD-1 — General Data

TTA075A

TTA085A

TTA100A

TTA100B

Cooling Performance

1

Gross Cooling Capacity, btu (kW)

Matched Air Handler (kW)

84,000(24.60)

90,000(26.35)

114,000(33.38)

112,000(32.79)

Condensing Unit Only

2

(kW)

84,000(24.60)

93,000(27.23)

114,000(33.38)

112,000(32.79)

ARI Net Cooling Capacity

3

(kW)

81,000(23.72)

88,000(25.77)

110,000(32.21)

108,000(31.62)

System Power kW

7.81

7.867

10.27

10.06

Condensing Unit Power kW

7.05

7.07

9.26

9.13

Compressor
Number

1

1

1

2

Type

Trane 3-D® Scroll

Trane 3-D® Scroll

Trane 3-D® Scroll

Trane Climatuff

Scroll

No. Motors (each)

1

1

1

1

Motor HP (kW)

6.25 (4.7)

6.91(5.15)

8.33(6.21)

4.15(3.1)

Motor RPM

2875

2875

2875

2875

ARI Sound Rating (Bels)

4

8.8

8.8

8.8

8.8

System Data

5

No. Refrigerant Circuits

1

1

1

2

Suction Line in. (mm) OD

1.375(34.9)

1.375(34.9)

1.375(34.9)

1.125(28.58)

Liquid Line in. (mm) OD

0.500(12.7)

0.500(12.7)

0.500(12.7)

0.375(9.53)

Outdoor Coil — Type

Plate Fin

Plate Fin

Plate Fin

Plate Fin

Tube Size in. (mm) OD

0.375(9.5)

0.375(9.5)

0.375(9.5)

0.375(9.53)

Face Area, sq. ft (m

2

)

19.25(1.79)

24.0(2.23)

24.0(2.23)

24.0(2.23)

Rows

2

2

2

2

Fins Per Inch

18

20

20

20

Outdoor Fan Type

Propeller

Propeller

Propeller

Propeller

No. Used

1

1

1

1

Diameter in. (mm)

26.00(660.4)

28.00(711.2)

28.00(711.2)

28.00(711.2)

Drive Type

Direct

Direct

Direct

Direct

No. Speeds

1

1

1

1

CFM

6

(m

3

/h)

4700(7985.30)

8120(13795.0)

8120(13795.0)

8120(13795.0)

No. Motors

1

1

1

1

Motor HP (kW)

0.33(.25)

0.75(.56)

0.75(.56)

0.75(.56)

Motor RPM

925

925

975

975

R-22 Refrigerant Charge, lb

7

(kg)

16.0(7.26)

19.0(8.62)

19.0(8.62)

21.0(9.53)

Notes:
1. Cooling Performance is rated at 95°F (35°C) ambient, 80°F (26.7°C) entering dry bulb, 67°F (19.4°C) entering wet bulb and nominal cfm listed. ARI rating cfm is 350 cfm/ton for

this product. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20%
of nominal cfm. Certified in accordance with the Unitary Large Equipment certification program, which is based on ARI Standard 340/360 or 365-00.

2. Condensing Unit Only Gross Cooling Capacity rated at 45°F (7.2°C) saturated suction temperature and at 95°F (35°C) ambient.
3. ARI Net Cooling Capacity is calculated with matched blower coil and 25 ft (7.2 m) of 1.375, 0.500 OD interconnecting tubing. EER and/or SEER are rated at ARI conditions and in

accordance with DOE test procedures. Integrated Part Load Value is based on ARI Standard 340/360 or 365-00. Units are rated at 80°F (26.7°C) ambient, 80°F (26.7°C) entering
dry bulb, and 67°F (19.4°C) entering wet bulb at ARI rated cfm.

4. Sound Rating shown is tested in accordance with ARI Standard 270.
5. System Data based on maximum linear length 80 ft (26.7 m) Maximum lift: suction 60 ft (18.3 m) liquid 60 ft (18.3 m) For greater lengths, refer to refrigerant piping applications

manual.

6. Outdoor Fan cfm is rated with standard air-dry coil outdoor.
7. Refrigerant (operating) charge is for condensing unit (all circuits) with matching blower coils and 25 ft (7.6 m) of interconnecting refrigerant lines.