Performance data system – Trane SS-PRC003-EN User Manual

Page 23

background image

23

SS-PRC003-EN

Performance
Data

System

Table PD-10 — Gross Cooling Capacities (MBh)

TTA125B Condensing Unit with TWE155B Air Handler

(I-P)

Ambient Temperature (°F)

85

95

105

115

Enter.
Dry

Entering Wet Bulb (°F)

CFM

Bulb

61

67

73

61

67

73

61

67

73

61

67

73

Airflow

(°F)

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

75

124.0

98.6 136.6 82.4 149.8 55.6

119.5

96.3 131.6 80.4 144.1 53.6 114.6 93.8 126.1 78.2 137.9 51.5 109.3 91.2 120.3 75.9 131.3 49.3

3750

80

124.7

115.3 136.9 94.8 150.4 73.4

120.2

113.0 131.9 92.5 144.8 71.3 115.5 110.6 126.5 90.1 138.9 69.1 110.5 108.1 120.8 87.5 132.5 66.8

85

128.0

128.0 137.5 111.4 151.0 90.7

124.2

124.2 132.5 109.1 145.4 88.7 120.1 120.1 127.1 106.7 139.5 86.5 115.6 115.6 121.4 104.1 132.8 83.5

90

134.5

134.5 138.2 128.2 151.2 107.1

130.6

130.6 133.3 125.9 145.7 104.9 126.3 126.3 128.2 123.6 139.9 102.5 121.7 121.7 122.8 121.1 133.6 100.0

75

126.6

103.5 139.2 81.3 152.2 56.6

121.9

101.2 134.0 79.1 146.3 54.6 116.9 98.7 128.4 76.8 140.0 52.4 111.4 96.0 121.9 73.8 133.2 50.2

4200

80

127.6

122.0 139.6 99.3 153.0 76.1

123.1

119.7 134.4 97.0 147.3 74.0 118.3 117.3 128.8 94.5 141.2 71.8 113.1 113.1 122.9 91.8 134.6 69.4

85

132.5

132.5 140.2 117.6 153.7 95.2

128.5

128.5 135.0 115.3 147.6 92.4 124.1 124.1 129.5 112.8 141.5 90.0 119.4 119.4 123.6 110.2 135.0 87.4

90

139.3

139.3 141.3 136.2 154.0 112.9

135.1

135.1 136.4 133.9 148.3 110.6 130.6 130.6 130.7 130.7 142.2 108.2 125.8 125.8 125.9 125.9 135.8 105.6

75

128.8

108.2 141.4 84.2 154.2 57.7

123.9

105.8 136.0 82.1 148.1 55.6 118.7 103.3 129.7 79.0 141.6 53.4 113.1 100.5 123.6 76.3 134.6 51.0

4650

80

130.2

128.5 141.8 103.6 155.2 78.7

125.3

125.3 136.5 101.2 149.3 76.5 120.9 120.9 130.8 98.7 143.0 74.3 116.1 116.1 124.7 96.0 136.2 71.9

85

136.4

136.4 142.4 123.5 155.6 98.5

132.2

132.2 137.2 121.2 149.7 96.2 127.5 127.5 131.5 118.6 143.5 93.7 122.6 122.6 125.6 116.0 136.9 91.1

90

143.4

143.4 144.2 144.0 156.3 118.4

139.0

139.0 139.2 139.2 150.4 116.1 134.3 134.3 134.4 134.4 144.2 113.6 129.2 129.2 129.3 129.3 137.6 111.0

75

130.6

112.7 142.7 86.5 155.8 58.6

125.6

110.3 137.3 84.1 149.6 56.4 120.3 107.7 131.3 81.4 142.9 54.1 114.7 104.9 125.1 78.6 135.8 51.7

5100

80

132.5

132.5 143.7 107.7 157.0 81.1

128.3

128.3 138.3 105.3 151.0 79.0 123.7 123.7 132.4 102.7 144.5 76.7 118.8 118.8 126.2 100.0 137.6 74.4

85

139.7

139.7 144.4 129.2 157.5 102.2

135.4

135.4 139.1 126.9 151.5 99.9 130.6 130.6 133.3 124.3 145.2 97.3 125.5 125.5 127.3 121.7 138.4 94.7

90

147.0

147.0 147.2 147.2 158.2 123.7

142.5

142.5 142.6 142.6 152.2 121.3 137.6 137.6 137.7 137.7 145.9 118.8 132.3 132.3 132.4 132.4 139.1 116.2

Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.

All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity

Table PD-10 — Gross Cooling Capacities (kW)

TTA125B Condensing Unit with TWE155B Air Handler

(SI)

Ambient Temperature (°C)

29.4

35.0

40.6

46.1

Enter.
Dry

Entering Wet Bulb (°C)

m

3

/h

Bulb

16.1

19.4

22.8

16.1

19.4

22.8

16.1

19.4

22.8

16.1

19.4

22.8

Airflow

(°C)

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

24

36.3

28.9

40.0

24.1

43.9

16.3

35.0

28.2

38.5

23.5

42.2

15.7

33.6

27.5

36.9

22.9

40.4

15.1

32.0

26.7

35.2

22.2

38.5

14.4

6371

27

36.5

33.8

40.1

27.8

44.0

21.5

35.2

33.1

38.6

27.1

42.4

20.9

33.8

32.4

37.0

26.4

40.7

20.2

32.4

31.6

35.4

25.6

38.8

19.6

29

37.5

37.5

40.3

32.6

44.2

26.6

36.4

36.4

38.8

32.0

42.6

26.0

35.2

35.2

37.2

31.2

40.9

25.3

33.8

33.8

35.5

30.5

38.9

24.4

32

39.4

39.4

40.5

37.5

44.3

31.4

38.2

38.2

39.0

36.9

42.7

30.7

37.0

37.0

37.5

36.2

40.9

30.0

35.6

35.6

35.9

35.5

39.1

29.3

24

37.1

30.3

40.8

23.8

44.6

16.6

35.7

29.6

39.2

23.2

42.8

16.0

34.2

28.9

37.6

22.5

41.0

15.4

32.6

28.1

35.7

21.6

39.0

14.7

7136

27

37.4

35.7

40.9

29.1

44.8

22.3

36.0

35.1

39.4

28.4

43.1

21.7

34.6

34.3

37.7

27.7

41.3

21.0

33.1

33.1

36.0

26.9

39.4

20.3

29

38.8

38.8

41.0

34.4

45.0

27.9

37.6

37.6

39.5

33.7

43.2

27.1

36.3

36.3

37.9

33.0

41.4

26.3

35.0

35.0

36.2

32.3

39.5

25.6

32

40.8

40.8

41.4

39.9

45.1

33.1

39.6

39.6

39.9

39.2

43.4

32.4

38.2

38.2

38.3

38.3

41.7

31.7

36.8

36.8

36.9

36.9

39.8

30.9

24

37.7

31.7

41.4

24.7

45.1

16.9

36.3

31.0

39.8

24.0

43.4

16.3

34.8

30.2

38.0

23.1

41.5

15.6

33.1

29.4

36.2

22.3

39.4

14.9

7900

27

38.1

37.6

41.5

30.3

45.4

23.0

36.7

36.7

40.0

29.6

43.7

22.4

35.4

35.4

38.3

28.9

41.9

21.8

34.0

34.0

36.5

28.1

39.9

21.1

29

39.9

39.9

41.7

36.2

45.6

28.9

38.7

38.7

40.2

35.5

43.8

28.2

37.3

37.3

38.5

34.7

42.0

27.4

35.9

35.9

36.8

34.0

40.1

26.7

32

42.0

42.0

42.2

42.2

45.8

34.7

40.7

40.7

40.7

40.7

44.1

34.0

39.3

39.3

39.4

39.4

42.2

33.3

37.8

37.8

37.9

37.9

40.3

32.5

24

38.2

33.0

41.8

25.3

45.6

17.2

36.8

32.3

40.2

24.6

43.8

16.5

35.2

31.5

38.5

23.8

41.8

15.8

33.6

30.7

36.6

23.0

39.8

15.1

8665

27

38.8

38.8

42.1

31.5

46.0

23.8

37.6

37.6

40.5

30.8

44.2

23.1

36.2

36.2

38.8

30.1

42.3

22.5

34.8

34.8

37.0

29.3

40.3

21.8

29

40.9

40.9

42.3

37.8

46.1

29.9

39.6

39.6

40.7

37.1

44.4

29.2

38.2

38.2

39.0

36.4

42.5

28.5

36.7

36.7

37.3

35.6

40.5

27.7

32

43.0

43.0

43.1

43.1

46.3

36.2

41.7

41.7

41.8

41.8

44.6

35.5

40.3

40.3

40.3

40.3

42.7

34.8

38.7

38.7

38.8

38.8

40.7

34.0

Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.

All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity