Table PD-4 — Gross Cooling Capacities (MBh) TTA085A Condensing Unit with TWE100A Air Handler

(I-P)

Ambient Temperature (°F)

85

95

105

115

Enter.
Dry

Entering Wet Bulb (°F)

CFM

Bulb

61

67

73

61

67

73

61

67

73

61

67

73

Airflow

(°F)

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

75

87.7

68.7

97.0

57.2 107.1 39.2

84.5

67.1

93.5

55.8 103.1 37.9

81.1

65.4

89.8

54.3

98.9

36.4

77.6

63.7

86.0

52.7

94.6

35.0

2500

80

88.0

80.1

97.3

66.3 107.2 51.4

84.9

78.5

93.8

64.8 103.4 49.9

81.6

76.9

90.1

63.2

99.3

48.4

78.2

75.1

86.1

61.3

95.1

46.9

85

89.8

89.8

97.5

77.6 107.6 63.2

87.2

87.2

94.0

76.0 103.7 61.7

84.4

84.4

90.3

74.3

99.7

60.2

81.5

81.5

86.5

72.7

95.5

58.7

90

94.4

94.4

97.9

89.0 107.8 74.9

91.7

91.7

94.4

87.4 103.9 73.5

88.9

88.9

90.9

85.8

99.8

71.6

85.9

85.9

87.3

84.2

95.6

70.0

75

89.6

72.2

99.1

56.7 109.0 40.0

86.3

70.6

95.4

55.2 104.9 38.6

82.8

68.9

91.6

53.6 100.5 37.2

79.2

67.1

87.6

52.0

96.0

35.6

2800

80

90.2

84.8

99.4

69.7 109.3 53.3

87.0

83.2

95.5

67.8 105.3 51.8

83.7

81.6

91.7

66.2 101.1 50.3

80.2

79.9

87.8

64.4

96.7

48.7

85

93.1

93.1

99.5

81.9 109.6 66.3

90.4

90.4

95.9

80.3 105.6 64.8

87.4

87.4

92.1

78.6 101.5 63.3

84.4

84.4

88.2

76.9

97.1

61.7

90

98.0

98.0 100.2 94.6 109.7 78.8

95.1

95.1

96.7

93.0 105.7 77.2

92.1

92.1

93.1

91.4 101.6 75.6

89.0

89.0

89.1

89.1

97.3

73.9

75

91.2

75.5 100.7 58.8 110.5 40.8

87.8

73.9

96.9

57.3 106.2 39.4

84.2

72.1

93.0

55.7 101.8 37.9

80.5

70.3

88.9

54.1

97.2

36.3

3100

80

92.1

89.4 100.9 72.5 111.0 55.1

88.9

87.8

97.1

70.8 106.8 53.6

85.2

85.2

93.2

69.1 102.5 52.1

82.1

82.1

89.2

67.4

98.1

50.5

85

96.1

96.1 101.2 86.1 111.3 69.2

93.1

93.1

97.5

84.5 107.2 67.7

90.1

90.1

93.7

82.8 102.9 66.2

86.9

86.9

89.7

81.1

98.3

64.1

90

101.1

101.1 102.3 100.0 111.5 82.7

98.1

98.1

98.8

98.5 107.4 81.1

94.9

94.9

95.0

95.0 103.1 79.5

91.6

91.6

91.7

91.7

98.7

77.8

75

92.6

78.7 102.1 60.8 111.8 41.5

89.1

77.0

98.2

59.2 107.4 40.0

85.5

75.3

94.2

57.6 102.9 38.4

81.7

73.5

90.0

56.0

98.2

36.8

3400

80

93.9

93.8 102.3 75.4 112.4 56.8

90.5

90.5

98.5

73.7 108.1 55.3

87.4

87.4

94.5

72.0 103.7 53.8

84.1

84.1

90.3

70.2

99.2

52.2

85

98.6

98.6 102.7 90.1 112.8 72.0

95.6

95.6

99.0

88.5 108.3 70.1

92.4

92.4

95.0

86.8 104.0 68.5

89.0

89.0

91.0

85.1

99.4

66.7

90

103.8

103.8 103.9 103.9 112.9 86.4

100.7

100.7 100.8 100.8 108.7 84.8

97.4

97.4

97.5

97.5 104.4 83.2

94.0

94.0

94.0

94.0

99.9

81.4

Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.

All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity

Table PD-4 — Gross Cooling Capacities (kW) TTA085A Condensing Unit with TWE100A Air Handler

(SI)

Ambient Temperature (°C)

29.4

35.0

40.6

46.1

Enter.
Dry

Entering Wet Bulb (°C)

m

3

/h

Bulb

16.1

19.4

22.8

16.1

19.4

22.8

16.1

19.4

22.8

16.1

19.4

22.8

Airflow

(°C)

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

24

25.7

20.1

28.4

16.7

31.4

11.5

24.7

19.6

27.4

16.3

30.2

11.1

23.7

19.2

26.3

15.9

29.0

10.7

22.7

18.6

25.2

15.4

27.7

10.2

4248

27

25.8

23.4

28.5

19.4

31.4

15.1

24.9

23.0

27.5

19.0

30.3

14.6

23.9

22.5

26.4

18.5

29.1

14.2

22.9

22.0

25.2

18.0

27.9

13.7

29

26.3

26.3

28.5

22.7

31.5

18.5

25.5

25.5

27.5

22.2

30.4

18.1

24.7

24.7

26.4

21.8

29.2

17.6

23.9

23.9

25.3

21.3

28.0

17.2

32

27.6

27.6

28.7

26.1

31.6

21.9

26.8

26.8

27.7

25.6

30.4

21.5

26.0

26.0

26.6

25.1

29.2

21.0

25.1

25.1

25.6

24.7

28.0

20.5

24

26.2

21.1

29.0

16.6

31.9

11.7

25.3

20.7

27.9

16.2

30.7

11.3

24.2

20.2

26.8

15.7

29.4

10.9

23.2

19.6

25.6

15.2

28.1

10.4

4757

27

26.4

24.8

29.1

20.4

32.0

15.6

25.5

24.4

28.0

19.9

30.8

15.2

24.5

23.9

26.9

19.4

29.6

14.7

23.5

23.4

25.7

18.9

28.3

14.3

29

27.3

27.3

29.1

24.0

32.1

19.4

26.5

26.5

28.1

23.5

30.9

19.0

25.6

25.6

27.0

23.0

29.7

18.5

24.7

24.7

25.8

22.5

28.4

18.1

32

28.7

28.7

29.3

27.7

32.1

23.1

27.9

27.9

28.3

27.2

31.0

22.6

27.0

27.0

27.3

26.8

29.8

22.1

26.1

26.1

26.1

26.1

28.5

21.7

24

26.7

22.1

29.5

17.2

32.4

12.0

25.7

21.6

28.4

16.8

31.1

11.5

24.7

21.1

27.2

16.3

29.8

11.1

23.6

20.6

26.0

15.8

28.5

10.6

5267

27

27.0

26.2

29.5

21.2

32.5

16.1

26.0

25.7

28.4

20.7

31.3

15.7

25.0

25.0

27.3

20.2

30.0

15.2

24.0

24.0

26.1

19.7

28.7

14.8

29

28.1

28.1

29.6

25.2

32.6

20.3

27.3

27.3

28.5

24.7

31.4

19.8

26.4

26.4

27.4

24.2

30.1

19.4

25.4

25.4

26.3

23.7

28.8

18.8

32

29.6

29.6

30.0

29.3

32.6

24.2

28.7

28.7

28.9

28.8

31.4

23.7

27.8

27.8

27.8

27.8

30.2

23.3

26.8

26.8

26.9

26.9

28.9

22.8

24

27.1

23.1

29.9

17.8

32.7

12.1

26.1

22.6

28.8

17.3

31.5

11.7

25.0

22.0

27.6

16.9

30.1

11.2

23.9

21.5

26.4

16.4

28.8

10.8

5777

27

27.5

27.5

30.0

22.1

32.9

16.6

26.5

26.5

28.8

21.6

31.7

16.2

25.6

25.6

27.7

21.1

30.4

15.7

24.6

24.6

26.4

20.6

29.0

15.3

29

28.9

28.9

30.1

26.4

33.0

21.1

28.0

28.0

29.0

25.9

31.7

20.5

27.0

27.0

27.8

25.4

30.4

20.0

26.1

26.1

26.6

24.9

29.1

19.5

32

30.4

30.4

30.4

30.4

33.1

25.3

29.5

29.5

29.5

29.5

31.8

24.8

28.5

28.5

28.6

28.6

30.6

24.4

27.5

27.5

27.5

27.5

29.2

23.8

Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.

All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity