Chapter 2 Installation

37

Installing the Breaker Interface Panel for the Ethernet Routing Switch 8010co Chassis

To install the BIP:

1

Remove the plastic back cover from the BIP terminal block (

Figure 16

).

Figure 16 Removing the plastic back cover from the BIP

2

Position the BIP in the uppermost position in the rack and align the holes in
the mounting bracket with the holes in the rack.

3

Insert 2 screws, appropriate for your rack type, into each mounting bracket
and tighten them (

Figure 17

).

Figure 17 Installing the BIP in the rack

4

After the BIP is secured in the rack, go to the next section,

“Connecting cables

to the chassis power supplies” on page 38

.

Caution: The BIP weighs 33.9 lbs (15.4 kg). The next step requires two
persons to mount the BIP in the rack.

10421EA

1 = Back cover (plastic)
2 = Cover screws (x 4)