Rout_in (mode shedding, process), Rout_out (process), Rs_state (diagnostic, process) – National Instruments FP-3000 User Manual
Page 97: Table b-11. device states, Sel_1 through sel_3 (process, scaling, tuning), Sel_type (scaling)

Appendix B
Fieldbus Parameters
© National Instruments Corporation
B-19
FieldPoint FP-3000 User Manual
Caution
Using
Restart to Defaults
causes all your configured parameters in the
FP-3000 to revert to their factory default settings.
ROUT_IN (Mode Shedding, Process)
The cascade input set by a remote host. This is propagated to the output of
the block when it is in
ROut
mode. If the block is in
ROut
mode and this
parameter is not updated in
SHED_ROUT
time (a parameter in the resource
block), the block enters mode shedding. Mode shedding allows the block to
degrade from
ROut
mode into some higher priority mode.
ROUT_OUT (Process)
This is the back calculation output used by the host when trying to establish
a remote output loop. While the loop is being established, it is the current
value of the output channel and can be used by the host to initialize for
smooth transfer of control.
RS_STATE (Diagnostic, Process)
The current state of the device.
SEL_1 through SEL_3 (Process, Scaling, Tuning)
Input values for the selector.
SEL_TYPE (Scaling)
Defines the selector action—High, Medium, or Low.
Table B-11. Device States
State
Meaning
Start/Restart
The device has just started a restart cycle.
Initialization
The device is performing startup diagnostics.
Failure
A hardware failure has been detected.
On-Line Linking
The device is online and waiting for new parameter linkages to be
established.
On-Line
The device is online and in service.
Standby
The device is online, but currently out of service.