beautypg.com

Actual mode, Permitted mode, Normal mode – National Instruments FP-3000 User Manual

Page 75: Table 4-9. modes, Actual mode -23 permitted mode -23 normal mode -23

background image

Chapter 4

Block Reference

© National Instruments Corporation

4-23

FieldPoint FP-3000 User Manual

ACTUAL Mode

An indicator of the current mode of execution of the device. This is a
read-only parameter. Normally, the actual mode of the block is equal to the
target mode of the block. However, configuration errors or other conditions
can cause it to differ from the target mode.

PERMITTED Mode

A list describing the modes into which the block may be target. For
example, in order to set a

TARGET

mode of

Man

, the

Man

mode bit must be

set in the

PERMITTED

mode field. The

PERMITTED

mode field also has an

effect on the way output blocks shed modes. For a description of mode
shedding, refer to Appendix D,

Advanced Function Block Behavior

.

NORMAL Mode

The block’s normal mode of operation is stored in the

NORMAL

field. This

field is not used internally by the device, but is a guide for an operator.

Table 4-9. Modes

Mode

Meaning

Bit Set in TARGET Mode

Out of Service

OOS

(0x80)

The block is idle and does not execute. If the
resource block is out of service, all other
blocks in the device are also out of service.

Out of Service, and optionally
any other valid target mode

Manual

Man

(0x10)

The output of the block is set by an operator
through a write to the output parameter. No
block processing other than writing to the
I/O channel is performed.

Manual

Initialization
Manual

IMan

(0x40)

The upstream block in a cascade loop is
preparing to enter

Auto

mode. This mode

cannot be set as a target mode. It is used
internally by control blocks as they establish
cascade loops.

Not applicable

Local Override

LO

(0x20)

The block’s faultstate or interlock capability
is causing the block to override its normal
output value. This mode cannot be set as a
target mode.

Not applicable

Automatic

Auto

(0x08)

The block operates normally with a setpoint
specified manually through a write to the
setpoint parameter.

Automatic