Chapter 4

Block Reference

FieldPoint FP-3000 User Manual

4-24

www.ni.com

Cascade

Cas

(0x04)

The block operates normally with a setpoint
specified automatically through a
connection from an upstream block to the

CAS_IN

(cascade input) parameter. Before

the block can enter this mode, the cascade is
initialized automatically to avoid windup.

Cascade and Automatic

Remote Cascade

RCas

(0x02)

The block operates normally with a setpoint
specified automatically through a write from
a host computer to the

RCAS_IN

(remote

cascade input) parameter. Before the block
can enter this mode, the cascade is initialized
automatically to avoid windup.

Remote Cascade and
Automatic. For more
information on Remote
Cascade operation, refer to the
section

Fault State and Mode

Shedding

in Appendix D,

Advanced Function
Block Behavior

.

Remote Output

ROut

(0x01)

The output of the block is set manually
through a write to the

ROUT_IN

parameter.

No block processing other than writing to
the I/O channel is performed. Before the
block can enter this mode, the cascade is
initialized automatically to avoid windup.

Remote Output and Automatic.
For more information on
Remote Output operation, refer
to the section

Fault State and

Mode Shedding

in

Appendix D,

Advanced

Function Block Behavior

.

Table 4-9. Modes (Continued)

Mode

Meaning

Bit Set in TARGET Mode