Scale the PID

Double-click on the PID block you created to launch the block
configuration window. Set the

PV_SCALE

parameter on the Scaling tab.

The

PV_SCALE

should match the output scale (

OUT_SCALE

) of the AI block

because you will wire the output of the AI block to the

IN

(i.e., process

variable) of the PID block. Enter the following:

PV_SCALE

EU_100

1775

EU_0

-273

Units_Index °C

Decimal

2

When you set the

PV_SCALE

for the AO block, you set it to take 0 to 100

percent, so adjust the PID block to output that range. To set the

OUT_SCALE

parameter of the PID, enter the following:

OUT_SCALE

EU_100

100

EU_0

0

Units_Index %

Decimal

2

Set Up Scheduling

Before the block will operate, you need to schedule the block to execute.
All Fieldbus function blocks (including function blocks on the FP-3000)
execute according to a schedule. You can specify the order of function
blocks in the schedule and the rate at which the schedule is repeated. If the
Function Block Application Editor window is not already open,
double-click on Function Block Application in the configuration tree of
the NI-FBUS Configurator.

Connect the PID to the AI and AO Blocks

Drag your AI, AO, and PID blocks from the configuration tree to the
Function Block Application Editor window, if you have not done so
already. The NI-FBUS Configurator automatically generates a schedule for
the blocks that causes them to run every second (refer to the documentation
that came with your NI-FBUS Configurator for information about
changing the execution period).