Table b-1. error codes – National Instruments FP-3000 User Manual
Page 81
Appendix B
Fieldbus Parameters
© National Instruments Corporation
B-3
FieldPoint FP-3000 User Manual
Table B-1. Error Codes
Error Code
Code
Description
Other
0x0001
Undefined block error condition.
Block Configuration Error
0x0002
The block has detected an error in its
configuration. This usually indicates a
static parameter has been left uninitialized.
Link Configuration Error
0x0004
The logical connection between this block
and another block is misconfigured.
Simulate Active
0x0008
For I/O function blocks, this indicates that
simulation is enabled. For the resource
block, this indicates that the simulate
jumper has been set, allowing simulation
to be enabled in other blocks.
Local Override
0x0010
The block has locally overridden the
output value. This can be the result of an
interlock or faultstate.
Device Faultstate Set
0x0020
The block’s faultstate behavior is active.
Device Needs Maintenance
Soon
0x0040
The device is reporting performance
degradation that will soon require
maintenance.
Input Failure/BAD PV Status
0x0080
Either the input transducer channel has
reported a failure, or the input parameter
from an upstream block has reported a
failure. For an AI block, this could be
caused by an open circuit being detected
on the FP-AI-100 input module.
Output Failure
0x0100
The output transducer channel has reported
a failure. For an AO block, this could
indicate that the FP-AO-200 cannot drive
the current request, perhaps due to an open
circuit.
Memory Failure
0x0200
The storage for nonvolatile and static
parameters was corrupted.
Lost Static Data
0x0400
The device was unable to restore the values
of static parameters after a restart.