Appendix C

FP-3000 Specific Parameters

FieldPoint FP-3000 User Manual

C-10

www.ni.com

OP_CMD_CXO

The lowest level priority input. This can be used to allow the operator to
activate interlock behavior with a write from the host application.

RUN_STATUS

The current run status of the block (used for debugging).

RUN_TIME

The time the block took to run (including overhead).

SAFEGUARD_CL

An interlock input. When in

Discret_State_1

, the output of the block is

forced closed (

Discret_State_0

). This interlock input has priority over

all other interlock inputs.

SAFEGUARD_OP

An interlock input. When in

Discret_State_1

, the output of the block is

forced open (

Discret_State_1

). This interlock input has priority over all

other interlock inputs except

SAFEGUARD_CL

.

SUPPORTED_MODES

The modes supported by the block.

Table C-8. Command Parameters

Value

Description

Close

When this flag is set, the output of the block is forced to

Discret_State_0

. This interlock is overridden by every other

interlock. If both

OP_CMD_CXO.Close

and

OP_CMD_CXO.Open

are set,

they are both considered to be clear.

Open

When this flag is set, the output of the block is forced to

Discret_State_1

. This interlock is overridden by every other

interlock. If both

OP_CMD_CXO.Close

and

OP_CMD_CXO.Open

are set,

they are both considered to be clear.

Stop

Unused in FieldPoint.

Enable 1, 2, 3

Unused in FieldPoint.