Bypass (scaling, tuning), Cas_in (process), Cas_in_d (process) – National Instruments FP-3000 User Manual
Page 82: Channel (i/o, process)

Appendix B
Fieldbus Parameters
FieldPoint FP-3000 User Manual
B-4
www.ni.com
BYPASS (Scaling, Tuning)
Allows the normal control algorithm to be bypassed if the
CONTROL_OPT
parameter’s Bypass Enable option is selected. If control is bypassed, the
PID uses its setpoint value in percent of scale as its output value and does
not attempt to do any PID control.
CAS_IN (Process)
A remote setpoint value. If used, will be linked to an output of an upstream
block. In some blocks, may be left unlinked, and a local setpoint value
(typically SP) will be used instead.
CAS_IN_D (Process)
A remote setpoint value. If used, will be linked to an output of an upstream
block. In some blocks, may be left unlinked, and a local setpoint value
(typically
SP_D
) will be used instead.
CHANNEL (I/O, Process)
Used by I/O function blocks to select a physical I/O channel. This mapping
is defined by the manufacturer. In the FP-3000, this parameter is
automatically updated when the
FIELDPOINT_MODULE
and
FIELDPOINT_CHANNEL
parameters are modified.
Lost NV Data
0x0800
The device was unable to restore the values
of nonvolatile parameters after a restart.
Readback Check Failed
0x1000
The value read back from the output
channel does not match the value the
output channel was set to.
Device Needs Maintenance
Now
0x2000
The device needs to be maintained now.
Power-Up
0x4000
The device has just powered up.
Out of Service
0x8000
The block is currently out of service.
Table B-1. Error Codes (Continued)
Error Code
Code
Description