National Instruments FP-RTD-122 User Manual
Features
323348B-01
April 2003
© 2002–2003 National Instruments Corp. All rights reserved.
FieldPoint™, National Instruments™, NI™, and ni.com™ are trademarks of National Instruments Corporation.
Product and company names mentioned herein are trademarks or trade names of their respective companies.
For patents covering National Instruments products, refer to the appropriate location: Help»Patents in your software,
the patents.txt file on your CD, or ni.com/patents.
FieldPoint Operating Instructions
FP-RTD-122 and
cFP-RTD-122
Eight-Channel Three-Wire RTD and
Resistance Input Modules
These operating instructions describe how to install and use the
National Instruments FP-RTD-122 and cFP-RTD-122 three-wire
RTD and resistance input modules (referred to inclusively as the
[c]FP-RTD-122). For details on configuring and accessing the
[c]FP-RTD-122 over a network, refer to the user manual for the
FieldPoint network module you are using.
Features
The [c]FP-RTD-122 is a FieldPoint RTD and resistance input
module with the following features:
•
Inputs for 100 and 1,000
Ω platinum RTDs (resistance
temperature detectors)
•
Built-in linearization for six TCR (temperature coefficient of
resistance, or alpha) values of RTDs
•
Direct resistance measurements in 400 and 4,000
Ω ranges
•
True three-wire compensation
•
16-bit resolution
•
Filtering against 50 and 60 Hz noise
•
Hot swappable
•
2,300 V
rms
transient overvoltage protection
•
–40 to 70 °C operation
Document Outline
- FP-RTD-122 and cFP-RTD-122 Operating Instructions
- Features
- Installing the FP-RTD-122
- Installing the cFP-RTD-122
- Wiring the [c]FP-RTD-122
- Taking RTD Measurements with the [c]FP-RTD-122
- Measuring Resistance Directly
- Converting Resistance Measurements to Temperature Measurements
- Three-Wire Compensation of Lead Resistance Errors
- Status Indicators
- Upgrading the FieldPoint Firmware
- Isolation and Safety Guidelines
- Specifications
- Where to Go for Support