Cycle_sel (tuning), Cycle_type (tuning), Dd_resource (diagnostic) – National Instruments FP-3000 User Manual
Page 84: Dd_rev (diagnostic), Dev_rev (diagnostic), Dev_type (diagnostic), Disc_alm (alarming), Disc_lim (alarming)

Appendix B
Fieldbus Parameters
FieldPoint FP-3000 User Manual
B-6
www.ni.com
CYCLE_SEL (Tuning)
Identifies the block execution methods available. Unused in National
Instruments FP-3000.
CYCLE_TYPE (Tuning)
Used to select the block execution method. Unused in National Instruments
FP-3000.
DD_RESOURCE (Diagnostic)
Unused in FieldPoint.
DD_REV (Diagnostic)
The revision of the device description used by the device.
DEV_REV (Diagnostic)
The revision of the device.
DEV_TYPE (Diagnostic)
The manufacturer’s model number for the device.
DISC_ALM (Alarming)
The current state of the discrete alarm, along with a time and date stamp.
DISC_LIM (Alarming)
The discrete input state in which an alarm should be generated.
Use PV for BKCAL_OUT
When set, uses the process variable as the value for
BKCAL_OUT
, instead of the setpoint.
Obey SP Limits if Cas or
RCas
When set, confines the setpoint to values within
SP_HI_LIM
and
SP_LO_LIM
, even when the setpoint comes from another
function block.
No OUT Limits in Man
Unused in FieldPoint.
Table B-2. Control Options (Continued)
Options
Description