beautypg.com

Configuring the raven, At the polling host for modbus on udp, Configure the listening/device ports – Sierra Wireless RAVEN 1X 20070914 User Manual

Page 84

background image

Configuring Modbus/BSAP

Rev 3.0B Feb.08

79

The remote Raven then disassembles the packet before trans‐
mitting the RTU ID and serial data to the remote unit. The 
remote units operate in normal UDP mode and their data is 
sent to the host via the remote Raven and host Raven.

Configuring the Raven at the
Polling Host for Modbus on
UDP

This section covers a Polling Host with standard Modbus, 
variations may need additional AT commands.

1. Configure the listening/device ports

In AceManager, select Misc in the side menu.

Figure 8-1: AceManager: Misc

The destination port for the modem at the host needs to match 
the device port (*DPORT) in use on all the modems at the 
remote sites. For example, if the remote modem’s device port 
(*DPORT) is “12345”, then the Modbus host modemʹs S53 
destination port should be set to “12345”. 

Take note of (or set) the Device Port setting in *DPORT to 
configure the destination port on the remote modems.