Operation

98

SIPART PS2 Manual

A5E00074631--06

Normally adjustment of the first three following parameters is com-

pletely sufficient to enable a positioner to be operated by an actuator.

If you wish to become familiar with all details of the positioner, try out

incrementally the effects of the remaining parameters by selective

trials.

.

NOTE
In particular if the positioner has previously been operated using a

different actuator, it must always be reinitialized in order to restore the

factory settings. Only in this way can the positioner matching process

start from known conditions. The parameter “55.PRST” is provided for

this purpose.
This is also recommended if multiple parameters have been changed

in a single session, the effects cannot be assessed and unintended

consequences may result.

Positioning actuator type
This is to match the positioner with the respective actuator and where

necessary to the position sensor being used. The following adjustment

capabilities are provided:

S

YFCT = turn
This adjustment is necessary for the part-turn actuator.
If “turn” is selected, the following parameter “2. YAGL” is automati-

cally set to 90_ and cannot be changed.

S

YFCT = WAY (Factory setting)
This is necessary for a linear actuator. This allows the positioner to

compensate for the non-linearity that arises due to the conversion of

the linear movement of the linear actuator into the part-turn move-

ment of the feedback shaft. For this the positioner is factory set so

that it shows between “P 49.0 and P 51.0” when the arm on the

feedback shaft is vertical to the linear actuator spindle.

S

YFCT = LWAY
This must be adjusted, if an external linear potentiometer is to be

connected to a linear actuator.
TIP: use this adjustment also for part-turn actuators with reverse

direction of control action.

S

YFCT = ncSt
Use this when an NCS is fitted to a part-turn actuator.

S

YFCT = -ncSt
This must be set when an NCS is used with a part-turn actuator with

reverse direction of control action.

S

YFCT = ncSL
This must be set when an NCS is used with a linear actuator.

1.YFCT